enteliZONE Database Configuration Objects
Page 78 of 84
eZFC-424R4-24 Application Guide
Edition 2.6
Object Name
Object
Ref
Default
Description
HeatCool
ChangeoverDelay
AV104
5
minutes
Time delay between heating and cooling to
prevent overshoot when the heating and
cooling setpoints are close together. Range
between 1 to 30 minutes.
Standby Setback
AV105
1
Celsius
Extra setpoint offset added in standby mode.
EcoMode Setback
AV106
1
Celsius
Amount of setback that gets subtracted from
heating and added the cooling setpoints when
controller is in eco mode.
OccSetpoint Off-
setRange
AV107
3
Celsius
Determines the offset range available to
change the Occupied Heating and Cooling
setpoints at a LINKnet stat interface or a
hardwired setpoint adjust input.
OATHeat Lock-
outSetpoint
AV160
99
Celsius
Outside air temperature heat lockout setpoint.
DATHiLimit Set-
pointDiff
AV161
25
Celsius
Discharge air temperature high limit setpoint
differential.
HeatingDemandLimit
AV163
100%
Heating demand limit.
OATCool Lock-
outSetpoint
AV165
-99
Celsius
Outside air temperature cooling lockout
setpoint. Not used by VAV/VVT systems.
DATLowLimit Set-
pointDiff
AV166
15
Celsius
Discharge air temperature low limit setpoint.
CoolingDemand
Limit
AV167
100%
Cooling demand limit.
CO2OccOnSetpoint
AV182
900
ppm
CO2 high limit occupancy setpoint.
CO2OccOffSetpoint
AV183
700
ppm
CO2 low limit occupancy setpoint.
CO2Demand
VentSetpoint
AV185
1100
ppm
CO2 demand ventilation setpoint.
Summary of Contents for eZFC-424R4-24
Page 1: ...eZFC 424R4 24 Application Guide Edition 2 6...
Page 67: ...enteliZONE Sequence of Operations Page 66 of 84 eZFC 424R4 24 Application Guide Edition 2 6...
Page 70: ...eZFC 424R4 24 Application Guide Edition 2 6 Page 69 of 84...
Page 71: ...enteliZONE Sequence of Operations Page 70 of 84 eZFC 424R4 24 Application Guide Edition 2 6...