enteliZONE Database Configuration Objects
Page 74 of 84
eZFC-424R4-24 Application Guide
Edition 2.6
Object Name
Object Ref
Default
Description
Damper1 Feed-
back
AV13
0 %
Position feedback signal from a
damper.
FanSpdCtrl
AV1
(ManualFanSpeedCmd)
%
Manual supply fan input.
FanSpdSwitch
OffResistance
AV192
0 kohm
Resistance of the fan speed
switch when it is in the off
position.
FanSpdSwitch
AutoResistance
AV193
100,000
kohm
Resistance of the fan speed
switch when it is in the Auto
position.
FanSpdSwitch
Fan1Resistance
AV194
5 kohm
Resistance of the fan speed
switch when it is in the Fan
Speed 1 position.
FanSpdSwitch
Fan2Resistance
AV195
10 kohm
Resistance of the fan speed
switch when it is in the Fan
Speed 2 position.
FanSpdSwitch
Fan3Resistance
AV196
30 kohm
Resistance of the fan speed
switch when it is in the Fan
Speed 3 position.
FanStatus
MV7
NotUsed_
Status of the zone supply fan.
WindowContact
MV6
NotUsed_
Window contact to detect open
windows in order to control
local heating or cooling.
Condensate
Switch
MV9
NotUsed_
Used to disable cooling when
condensate is detected in the
bottom of the unit.
Fault
MV10
NotUsed_
Used to display equipment
working status.
Filter Status
MV11
NotUsed_
Switch placed across an air
filter to provide a signal to let
operators know when it is time
to change the filter.
HeatCool
ChangeOver
Status
MV803
NotUsed_
The output status of the 2-pipe
fan coil.
Summary of Contents for eZFC-424R4-24
Page 1: ...eZFC 424R4 24 Application Guide Edition 2 6...
Page 67: ...enteliZONE Sequence of Operations Page 66 of 84 eZFC 424R4 24 Application Guide Edition 2 6...
Page 70: ...eZFC 424R4 24 Application Guide Edition 2 6 Page 69 of 84...
Page 71: ...enteliZONE Sequence of Operations Page 70 of 84 eZFC 424R4 24 Application Guide Edition 2 6...