eZFC-424R4-24 Application Guide
Edition 2.6
Page 31 of 84
Setting Up a Condensate Level Switch
This input is used for a level switch in a condensate pan which alerts the system when a specific
water level in the pan has been exceeded. When the condensate input is active, the algorithm
automatically turns off any active ductal cooling stage to prevent the condensate pan from
overflowing.
1. Next to the input number that you’ve assigned to the condensate pump or control, in the
Function field, select
CondensateSwitch
.
2. In the Action/Scale field, choose between direct or reverse control.
3. (enteliWEB only) The Input Name field displays the object's name. You can change this
name by clearing the field and entering a new name.
Setting Up Other Supporting Inputs
This topic describes how to set up supporting inputs like fault and window monitoring using the
Local Inputs tab on the configuration page
Set Up an Input
1. Next to the input number that you've assigned to the device, in the Function field, select the
option that applies to your setup:
Function
Select this option if you are using a:
AnalogMUX_
Creating an analog input that will be used for monitoring and
will not be used by the algorithm in the controller.
BinaryMUX_
Creating an binary input that will be used for monitoring and
will not be used by the algorithm in the controller.
WindowContact_
Setting up a window contact switch to detect open windows.
When an open window is detected, local heating or cooling
can be disabled as needed to save energy.
FilterStatus_
Adding a filter switch to detect if the fan coil filter is clean or
dirty.
Fault_
Creating an input to monitor the fault status of an equipment.
SpaceTempSetpoint_
Resistive slider or dial to control the space setpoint. The
resistance range must be within 0 to 20 kohms.
2. Select the associated action/scale option for the input.
3. If you had selected the SpaceTempSetpoint_ option to set up a resistive slider, in additional
settings, in the
SetpointSliderMinResistance
field, enter the minimum resistance of the
Summary of Contents for eZFC-424R4-24
Page 1: ...eZFC 424R4 24 Application Guide Edition 2 6...
Page 67: ...enteliZONE Sequence of Operations Page 66 of 84 eZFC 424R4 24 Application Guide Edition 2 6...
Page 70: ...eZFC 424R4 24 Application Guide Edition 2 6 Page 69 of 84...
Page 71: ...enteliZONE Sequence of Operations Page 70 of 84 eZFC 424R4 24 Application Guide Edition 2 6...