61
Serial Interface Operation
|
power command
Use this command to retrieve or clear the power readings for current consumption and peak consumption watts.
Usage
rPDU>power [reset | summary]
where:
[reset]
= Clears the peak consumption watts to zero
[summary]
= Current consumption reading in watts (W), followed by the peak consumption power
reading in watts (W), separated by commas
Retrieve current consumption and peak consumption watts power readings
rPDU>power
Example
rPDU>power
rPDU: Power: 1.0W. Peak Consumption Watts: 2.0W.
Retrieve a summary of current consumption and peak consumption watts power readings
rPDU>power [summary]
Example
rPDU>power summary
rPDU: 1.0W,2.0W,0.0W,0.0W
NOTE:
The summary command response shows the present power as the first parameter and the peak consumption
watts as the second parameter. The minimum and average values will always be reported as zero.
Reset the peak consumption watts power readings to zero
rPDU>power [reset]
Example
rPDU>power summary
rPDU: 1.0W,2.0W,0.0W,0.0W
rPDU>power reset
rPDU:Clearing peak consumption watts to zero.
reboot command
Use this command to reboot the rPDU.
Usage
rPDU>reboot
Reboot the rPDU
rPDU>reboot
Examples
rPDU>reboot
Saving configuration to flash on rPDU ... Done ...
Username: