47
LCD Operation
|
Table 11. Settings (Continued)
Setting Option
Default Setting
Available Settings
Settings
Submenu
Power Limits
Near Overload Warning Level
[0kW]...[17.3kW] *
[0kW]...[22.0kW] **
[0kW]...[11.0kW] ***
An input wattage (kW) reading in excess of this
value causes an overload warning to generate.
This warning indicates that the current kW
reading has risen nearly to the overload alarm
level value.
13.8kW
17.6kW
8.8kW
Overload Alarm Level
[0kW]...[17.3kW] *
[0kW]...[22.0kW] **
[0kW]...[11.0kW] ***
An input wattage (kW) reading in excess of this
value causes an overload alarm to generate.
17.3kW
22.0kW
11.0kW
Low Load Warning Level
[0.0kW]...[17.3kW] *
[0.0kW]...[22.0kW] **
[0.0kW]...[11.0kW] ***
An input wattage (kW) reading less than this
value causes a low load warning to generate as a
reminder to share the load for this phase.
0.0kW
0.0kW
0.0kW
Environments
Temperature High Warning
Level
[0 degree C]...[65 degree C]
A high temperature warning threshold is
exceeded when a value greater than this setting
is detected by the environmental temperature
sensor. A high temperature warning generates.
59 degree C
Temperature High Alarm Level
[0 degree C]...[65 degree C]
A high temperature alarm threshold is exceeded
when a value greater than this setting is
detected by the environmental temperature
sensor. A high temperature alarm generates.
60 degree C
Humidity Low Warning Level
[0%]...[95%]
A low humidity warning threshold is exceeded
when a value less than this setting is detected
by the environmental humidity sensor. A low
humidity warning generates.
10%
Humidity Low Alarm Level
[0%]...[95%]
A low humidity alarm threshold is exceeded
when a value less than this setting is detected
by the environmental humidity sensor. A low
humidity alarm generates.
0%
* DELLM0001, DELLM001A, DELLM0004, DELLM004A, DELLM0006
** DELLM0002, DELLM0005, DELLM0007
*** DELLM0003
NOTE:
For Delta models, L1 represents L1-L3 data, L2 represents L1-L2 data, and L3 represents L2-L3 data.