Standard operating temperature
Table 23. Standard operating temperature specifications
Standard operating temperature
Specifications
Continuous operation (for altitude less than 950 m or
3117 ft)
10°C to 35°C (50°F to 95°F) with no direct sunlight on the
equipment.
Expanded operating temperature
Table 24. Expanded operating temperature specifications
Expanded operating temperature
Specifications
Continuous operation
5°C to 40°C at 5% to 85% RH with 29°C dew point.
NOTE:
Outside the standard operating temperature (10°C to
35°C), the system can operate continuously in temperatures as low
as 5°C and as high as 40°C.
For temperatures between 35°C and 40°C, de-rate maximum
allowable temperature by 1°C per 175 m above 950 m (1°F per 319 ft).
≤ 1% of annual operating hours
–5°C to 45°C at 5% to 90% RH with 29°C dew point.
NOTE:
Outside the standard operating temperature (10°C to
35°C), the system can operate down to –5°C or up to 45°C for a
maximum of 1% of its annual operating hours.
For temperatures between 40°C and 45°C,de-rate maximum allowable
temperature by 1°C per 125 m above 950 m (1°F per 228 ft).
NOTE:
When operating in the expanded temperature range, system performance may be impacted.
NOTE:
When operating in the expanded temperature range, ambient temperature warnings maybe reported in the System
Event Log.
Expanded operating temperature restrictions and Fresh Air restrictions
●
Six hot swappable fans (standard fans) are required.
●
Two PSUs in redundancy mode are required, but PSU failure is not supported.
●
3.5-inch x 18 hard drives is not supported.
●
NVMe or PCIe SSD is not supported.
●
GPGPU is not supported.
●
Processor > 165 W is not supported.
●
Internal TBU (tape backup drive) is not supported.
●
Non-Dell qualified peripheral cards are not supported.
●
Peripheral cards consuming greater than 25 W are not supported.
●
128 GB LRDIMM is supported.
●
NVDIMM is not supported.
●
Mellanox 100 GB, Mellanox Navi DP/SP, Intel FortPond Solarflare Nova, Solarflare Sunspot are not supported.
Particulate and gaseous contamination specifications
The following table defines the limitations that help avoid any equipment damage or failure from particulate and gaseous
contamination. If the levels of particulate or gaseous pollution exceed the specified limitations and result in equipment damage
or failure, you may need to rectify the environmental conditions. Remediation of environmental conditions is the responsibility of
the customer.
36
Technical specifications
Summary of Contents for 5WC10
Page 21: ...Figure 16 Configuration and layout Dell EMC PowerEdge T640 overview 21 ...
Page 22: ...Figure 17 Electrical overview 22 Dell EMC PowerEdge T640 overview ...
Page 23: ...Figure 18 Memory information Dell EMC PowerEdge T640 overview 23 ...
Page 24: ...Figure 19 System tasks 24 Dell EMC PowerEdge T640 overview ...