56
Code 240.010.0001
DLS 300 / 450 / 600
ALARM
TYPE
SOLUTION
E012
Mains voltage too high
•
Make sure that the mains voltage is within the range required by
local legislation.
•
Check the mains impedance.
•
If the voltage is outside the allowed range because of the conditions
of the local grid, contact the electricity provider to find out whether
the voltages at the connection point can be adjusted or ask for their
approval to change the operating limits.
•
If the voltage is within the allowed range, but the alarm persists,
contact our technical support service.
E013
Mains voltage too low
•
Make sure that the mains voltage is within the range allowed by lo-
cal legislation.
•
Check the mains impedance.
•
If the voltage is outside the allowed range because of the conditions
of the local grid, contact the electricity provider to find out whether
the voltages at the connection point can be adjusted or ask for their
approval to change the operating limits.
•
If the voltage is within the allowed range, but the alarm persists,
contact our technical support service.
E014
Mains voltage too low
•
Make sure that the mains voltage is within the range allowed by lo-
cal legislation.
•
Check the mains impedance.
•
If the voltage is outside the allowed range because of the conditions
of the local grid, contact the electricity provider to find out whether
the voltages at the connection point can be adjusted or ask for their
approval to change the operating limits.
•
If the voltage is within the allowed range, but the alarm persists,
contact our technical support service.
E015
Mains frequency too high
•
Make sure that the mains frequency is within the range allowed by
local legislation.
•
If the mains frequency is outside the allowed range because of the
conditions of the local grid, contact the electricity provider to ask for
their approval to change the operating limits.
•
If the mains frequency is within the allowed range, but the alarm
persists, contact our technical support service.
E016
Mains frequency too low
•
Make sure that the mains frequency is within the range allowed by
local legislation.
•
If the mains frequency is outside the allowed range because of the
conditions of the local grid, contact the electricity provider to ask for
their approval to change the operating limits.
•
If the mains frequency is within the allowed range, but the alarm
persists, contact our technical support service.
E017
Mains frequency too high
•
Make sure that the mains frequency is within the range allowed by
local legislation.
•
If the mains frequency is outside the allowed range because of the
conditions of the local grid, contact the electricity provider to ask for
their approval to change the operating limits.
•
If the mains frequency is within the allowed range, but the alarm
persists, contact our technical support service.