DLS 300 / 450 / 600
37
Code 240.010.0001
4.7
Switching on the System
1.
Close the connection compartment with its cover and secure it with fixing screws.
2. Switch on the AC line external main switch.
3. Switch on the DC isolator (position 1).
4. Wait until the display goes on.
5. Switch on the AC GRID magnetic thermal circuit breaker (position 1).
6. Program the system (please refer to the relevant section)
7. Switch on the AC OUT magnetic thermal circuit breaker (position 1).
8. Switch on the GEN magnetic thermal circuit breaker (optional) (position 1).
9. Switch off the AC BYPASS switch (position 0).
10. Carry out the AUTO-TEST (Italy– CEI 0-21) - The self-test is relevant only in Italy (CEI-021). If the
country is configured for Italy, the self-test is available through the service menu on the display. The
self-test for Italy aims to check the upper and lower limits for the mains voltage and frequency which,
if exceeded, will disconnected the DLS from the grid. Should the self-test fail, the DLS will not be con-
nected to the electricity grid.