DLS 300 / 450 / 600
57
Code 240.010.0001
ALARM
TYPE
SOLUTION
E018
Mains frequency too low
•
Make sure that the mains frequency is within the range allowed by
local legislation.
•
If the mains frequency is outside the allowed range because of the
conditions of the local grid, contact the electricity provider to ask for
their approval to change the operating limits.
•
If the mains frequency is within the allowed range, but the alarm
persists, contact our technical support service.
E019
Disconnection from the
grid controlled by the elec-
tricity provider.
•
Interface intervention required by the electricity provider .
E020
The direct current going
into the grid has a value
higher than the allowed
threshold.
•
Make sure that there is direct current going into the grid.
•
If the direct current going into the grid is outside the allowed range
because of the conditions of the local grid, contact the electricity
provider to ask for their approval to change the operating limits.
•
If the direct current going into the grid is within the allowed range,
but the alarm persists, contact our technical support service.
E021
The direct current going
into the grid has a value
higher than the maximum
instantaneous threshold
allowed.
•
Make sure that there is direct current going into the grid.
•
If the direct current going into the grid is outside the allowed range
because of the conditions of the local grid, contact the electricity
provider to ask for their approval to change the operating limits.
•
If the direct current going into the grid is within the allowed range,
but the alarm persists, contact our technical support service.
E022
Converter monitoring sys-
tem fault.
•
Switch off and restart the system.
•
Refer to the sections “Switching off the system” and “Switching on
the system”
•
Should the problem persist, contact our technical support service.
E023
DC overcurrent.
•
Check the sizes and the connection at the system DC inputs.
•
Refer to the section “Connection”.
•
Should the problem persist, contact our technical support service.
E024
DC overcurrent.
•
Check the sizes and the connection at the system DC inputs.
•
Refer to the section “Connection”.
•
Should the problem persist, contact our technical support service.
E025
Loss of isolation of the PV
generator.
•
Check the DC lines leakage to ground
E026
DC voltage out of range
•
Immediately disconnect the PV generator as it could get damaged.
•
Check the sizes of the system.
•
Check the PV generator no-load voltage.
E027
BATTERY overcurrent.
•
Check the sizes and the connections at the system BATTERY in-
puts.
•
Refer to the section “Connection”.
•
Should the problem persist, contact our technical support service.
E028
Unidentified battery.
•
Check the connections and the polarity at the system BATTERY
inputs.
•
Check the battery voltage and make sure that it is within the allowed
operating limits.
•
Refer to the section “Connection”.
•
Should the problem persist, contact our technical support service.