![Deif SGC 120 User Manual Download Page 49](http://html1.mh-extra.com/html/deif/sgc-120/sgc-120_user-manual_2465265049.webp)
Byte
Field
Remarks
4
Number of registers to read - high byte
Number of registers to read must be between 1 to 255
5
Number of registers to read - low byte
6/7
Error check CRC
Normal response from SGC 120/121 slave for Function 3
Byte
Field
Remarks
0
Slave address
As configured in the controller.
1
Function code (0x03)
2
Byte count (n)
Equals to number of registers to be read times two. 8-
bit even number between 2 to 250.
3
First register - high byte
Number of registers that have been written.
4
First register - low byte
...
...
1+n
Last register - high byte
2+n
Last register - low byte
3+2n/4+2n
Error check CRC
10.2 Register map (function code 03)
Register
address
Parameter
Scale factor
Unit/
Interpretation
Bits/Sign
0
Protocol revision
-
-
Unsigned
1
Generator L1-N voltage
0.1
V
Unsigned
2
Generator L2-N voltage
0.1
V
Unsigned
3
Generator L3-N voltage
0.1
V
Unsigned
4
Generator L1-L2 voltage
0.1
V
Unsigned
5
Generator L2-L3 voltage
0.1
V
Unsigned
6
Generator L3-L1 voltage
0.1
V
Unsigned
7
Generator L1 frequency
0.1
Hz
Unsigned
8
Generator L2 frequency
0.1
Hz
Unsigned
9
Generator L3 frequency
0.1
Hz
Unsigned
10
Generator power factor L1
0.01
--
Unsigned
11
Generator power factor L2
0.01
--
Unsigned
12
Generator power factor L3
0.01
--
Unsigned
13
Generator average power factor
0.01
--
Unsigned
14
Mains L1-N voltage
0.1
V
Unsigned
15
Mains L2-N voltage
0.1
V
Unsigned
16
Mains L3-N voltage
0.1
V
Unsigned
17
Mains L1-L2 voltage
0.1
V
Unsigned
18
Mains L2-L3 voltage
0.1
V
Unsigned
19
Mains L3-L1 voltage
0.1
V
Unsigned
USER MANUAL 4189341226A UK