![Deif SGC 120 User Manual Download Page 12](http://html1.mh-extra.com/html/deif/sgc-120/sgc-120_user-manual_2465265012.webp)
*SCP connections for Analogue input 2 used as
Fuel level sensor
with the reference configured as
Battery Negative
Battery
Sensor
input
Sensor
common
Terminal 2
Terminal 1
Supply
Analogue
resistive
sensor
SGC 1xx series
3.8 Analogue inputs used as digital inputs
Analogue inputs can be used as digital inputs when wired as shown.
F1
8-28
V DC
+
-
3.9 Analogue voltage/current input
Category
Specifications
Controller terminal
23
Measurement type
Analogue voltage/current sensing
Range
0 to 5 V DC
4 to 20 mA
Accuracy
±2 % of full scale voltage
±1.25 % of full scale current
Resolution
0.1 V
0.1 mA
USER MANUAL 4189341226A UK
Page 12 of 72