Level 2
Range
(LOAD TRANSFER DELAY)
Power Save Mode Delay
(PWR SAVE MODE DELAY)
5 to 1800 s
Screen Changeover Time
(SCRN CHNGOVER TIME)
1 to 1800 s
Deep Sleep Mode Delay
(DEEP SLP MODE DELAY)
5 to 1800 s
Sounder Alarm Time
(SOUNDER ALARM TIMER)
1 to 300 s
Auto Exit Config Mode
(AUTO EXIT CNFG MODE)
10 to 1800 s
6.2.7 Generator
Table 6.14
Alternator configuration (ALT CONFIG)
Level 2
Range
Alternator Present
(ALT PRESENT)
Yes
No
Number of Poles
(NUMBER OF POLES)
2/4/6/8
AC system
(ALT AC SYSTEM)
1 phase
3 phase
Min Healthy Voltage
(MIN HEALTHY VOLT)
50 to 350 V phase-neutral
Min Healthy Frequency
(MIN HEALTHY FREQ)
10 to 75 Hz
Phase Reversal Detection
(PHASE REVERSAL DETECT)
Enable
Disable
Phase Reversal Action
(PHASE REVERSAL ACTION)
None
Notification
Warning
Electrical Trip
Shutdown
Auto Load Transfer
(AUTO LOAD TRANSFER)
Enable
Disable
Table 6.15
Voltage Monitoring (VOLT MONITOR)
Level 2
Range
Under-voltage Shutdown
(UNDER VOLT SHUTDOWN)
Enable
Disable
Under-voltage Shutdown Threshold
(UV SHUTDOWN THRESH)
50 to 295 V phase-neutral
Under-voltage Warning
(UNDER VOLT WARNING)
Enable
Disable
Under-voltage Warning Threshold
(UV WARNING THRESHOLD)
55 to 300 V phase-neutral
USER MANUAL 4189341226A UK