Table 6.18
Load Monitoring (LOAD MONITOR)
Level 2
Range
Generator Rating
(GEN RATING)
0 to 8000 kW
Overload Action
(OVERLOAD ACTION)
None
Notification
Warning
Electrical Trip
Shutdown
Overload Threshold
(OVERLOAD THRESHOLD)
50 to 150 %
Overload Monitoring Delay
(OVERLOAD MON DELAY)
1 to 600 s
Unbalanced Load Action
(UNBAL LOAD ACTION)
None
Warning
Electrical Trip
Shutdown
Notification
Unbalanced Load Threshold
(UNBAL LOAD THRESHOLD)
5 to 200 %
Unbalanced Load Delay
(UNBAL LOAD DELAY)
1 to 600 s
6.2.8 Mains
Table 6.19
Configuration (MAINS CONFIG)
Level 2
Range
Mains Monitoring
(MAINS MONITORING)
Enable
Disable
Mains AC System
(MAINS AC SYSTEM)
1 phase
3 phase
Phase Reversal Detection
(PHASE REVERSAL DETECT)
Enable
Disable
Phase Reversal Action
(PHASE REVERSAL ACTION)
None
Notification
Partial Healthy Detection
(MAINS PARTIAL HEALTHY)
Enable
Disable
Table 6.20
Voltage Monitoring (VOLT MONITOR)
Level 2
Range
Under-voltage
(UV ENABLE)
Enable
Disable
(UV) Trip
(UV TRIP)
50 to 298 V phase-neutral
(UV) Return
(UV RETURN)
52 to 300 V phase-neutral
Over-voltage
(OV ENABLE)
Enable
Disable
USER MANUAL 4189341226A UK
Page 31 of 72