Page 16
Unless there is an abnormal condition,
do not attempt to remove the gas burner
taps. You must call an authorised
service agent if it is necessary to
change the taps.
New injectors have their position
marked on their packing or refer to the
Injector table.
Reduced gas flow rate setting for taps
1. Ignite the burner that is to be adjusted and turn the
knob to the reduced position.
2. Remove the knob from the gas tap.
3. Use an appropriately sized screwdriver to adjust
the flow rate adjustment screw. For LPG (Butane -
Propane) turn the screw clockwise. For natural
gas, you should turn the screw
counter-
clockwise
once. The normal length of a straight
flame in the reduced position should be 6-7 mm
4. If the flame is higher than the desired position, turn
the screw clockwise. If it is smaller turn
anticlockwise.
5. For the last control, bring the burner to both the
high-flame and reduced positions and check
whether the flame is on or off.
Depending on the type of gas tap used in your
appliance the adjustment screw position may vary.
1
Flow rate adjustment screw
Gas conversion
In order to have the appliance's gas type changed, all
the injectors must be changed and the flame
adjustment for all valves must be set at the reduced
flow rate position.
Changing the injectors
1. Take off burner cap and burner body.
2. Unscrew injectors by turning them
counterclockwise.
3. Fit new injectors.
4. Check all connections for secure fitting and
tightness.
DANGER Risk of
explosion or poisoning
by unprofessional
installation.
Gas
conversion must only be
carried out by a
registered installer.
DANGER Risk of
explosion!
Before starting any work
on the gas installation,
shut off the gas supply
.
1
Spark plug
2
Injector
3
Burner
If the gas type of the appliance is
changed, then the rating plate
that shows the gas type of the
unit must also be changed.
2
3
1