ZEN-LOG-MAN-16V03 (0930)
Copyright © 2016 Define Instruments
35
Connection example for an intelligent multiplexer
58
57
56
55
54
61
60
Zen
DI Com
DI 1
DI 2
AO Com
AO 1
DI 4
DI 3
PLC
Input Module
Analog
Input
PLC
Output Module
Open Collector
Output No 1
Open Collector
Output No 2
Open Collector
Output No 4
Open Collector
Output No 3
Regulated
Power Supply
24V DC
Note 1
In this configuration the DI Com
and digital inputs are isolated from the
inputs and outputs. The 24V external
power supply can therefore be used to
power transmitters connected to the Zen's
inputs.
Note 2
Each digital input draws 10mA at
24V DC.
Note 3
All cables must be screened,with
screen earthed at one end only.
Note 4
There is no limit to the number of
Zens that can be connected, except that
the power supply and open collector out-
puts must be able to handle the load.