Edit Configuration
39
4.6 TIMERS
Many timers are associated with alarms. Where this occurs, the timer for the alarm is located on the same
page as the alarm setting. Timers not associated with an alarm are located on the timers page.
The
timers
page is subdivided into smaller sections. Select the required section with the mouse.
4.6.1 START TIMERS
Timer
Description
Remote Start Off Load
Used to give a delay before starting in AUTO mode. This timer is activated upon the
respective start command being issued.
Typically this timer is applied to prevent starting upon fleeting remote start signals.
Remote Start On Load
Telemetry Start
Parameters detailed overleaf...
Click and drag to change the setting.
Timers increment in steps of 1 second up to one
minute, then in steps of 30 seconds up to 30
minutes, then in steps of 30 minutes thereafter
(where allowed by the limits of the timer).