Edit Configuration
109
4.14.2.2 FLAGS
A
flag
is
set
when a condition within the DSE controller is met. For instance, if the module is in
Auto
Mode an
internal flag is set. This flag is exposed as an
output source
when configuring module outputs and LEDs.
In addition to internal flags, a further forty (40) custom flags are available (named PLC Flag 1-40). These can
be used to ‘memorise’ that a condition has been met, and/or used to drive module outputs and LEDs’.
For example if a timer expires, a flag can be set to make a note of the timer expiring for later use in the ladder.
4.14.2.3 TIMERS
The PLC logic section contains ten (10) user timers for use in the ladder.
A timer is configured by clicking
in the menu bar. The ‘Edit time limits’ window appears.
A timer is used by adding the timer action to the ladder. When this action takes place, the timer begins.
Upon the timer reaching the configured ‘Timer limit’, a test for the timer will be successful:
Start Timer
Test Timer
Click and drag to change the time,
or press keyboard left and right
arrow keys to change by small
amounts.
Summary of Contents for DSE8810
Page 126: ...Scada 126 5 8 2 POWER Shows the module measurements of the supply power ...
Page 134: ...Scada 134 5 12 STATUS Shows the module s current status ...
Page 144: ...Scada 144 5 19 COMMUNICATIONS INFORMATION Shows the module s communication ports settings ...
Page 146: ...Scada 146 5 20 1 DATA LOG STATUS Shows the memory status of the data log allocated space ...