Scada
127
5.8.3 MULTISET
NOTE: These settings are not stored in the module configuration. They are stored in a different
memory area and not transferred with the configuration. The
Clone Module
feature transfers both the
configuration AND the settings of the Multiset, Governor/AVR interface and the Sync page.
Item
Function
KVAr control
The amount of reactive power that the set will produce when used in
‘load level control’ mode, when Reactive
Load Control Mode
is set to
Load Level Control
Pf control
The power factor that the set will maintain when used in ‘load level
control’ mode, when Reactive
Load Control Mode
is set to
Load
Level Control
)
NOTE: At low load levels, it may not be possible to
maintain the power factor.
Each controller connected to the MSC link
must have a unique ID.
If all the controllers are powered up “one at a
time”, this DeviceID is automatically set.
Powering them up together may result in “ID
alarm”. Manually setting the DeviceID here will
prevent this.
Set Priority used when
the
load demand
scheme
is in operation
Enable or disable the module’s
diagnostic Commissioning Screens.
Load levels used when ‘base load’ / ‘fixed export’
mode is in operation (see below for details)
The number of modules currently connected to
the MSC link
Summary of Contents for DSE8810
Page 126: ...Scada 126 5 8 2 POWER Shows the module measurements of the supply power ...
Page 134: ...Scada 134 5 12 STATUS Shows the module s current status ...
Page 144: ...Scada 144 5 19 COMMUNICATIONS INFORMATION Shows the module s communication ports settings ...
Page 146: ...Scada 146 5 20 1 DATA LOG STATUS Shows the memory status of the data log allocated space ...