Edit Configuration
34
Output source
Activates…
Is not active….
Low Oil Pressure Alarm
IEEE 37.2 - 63 pressure switch
Active when the
Oil Pressure
falls
below the
Low Oil Pressure Alarm
setting
Inactive when
•
The set is stopped
•
During starting sequence before
the safety delay time has
expired.
Low Oil Pressure Pre-Alarm
IEEE 37.2 - 63 pressure switch
Active when the
Oil Pressure
falls
below the
Low Oil Pressure Pre-
Alarm
setting
Inactive when
•
The set is stopped
•
During starting sequence before
the safety delay time has
expired.
Low Load
Indicates that the stopping sequence is beginning due to low load levels.
(
Load Demand Scheme
)
Manual Button Pressed
Active when the Manual button on the
front fascia is pressed
Inactive when the button is released
MPU open circuit
(Not applicable to 8860)
This output indicates that the module has detected an open circuit failure in
the Magnetic Pickup transducer circuit.
Main Config Selected
Indicates that the main configuration has been selected
Mains Decoupling High Frequency
This output indicates that the mains decoupling high frequency alarm has
been triggered.
Mains Decoupling High Voltage
This output indicates that the mains decoupling high voltage alarm has been
triggered.
Mains Decoupling Low Frequency
This output indicates that the mains decoupling low frequency alarm has been
triggered.
Mains Decoupling Low Voltage
This output indicates that the mains decoupling low voltage alarm has been
triggered.
Mains ROCOF
Indicates that the ROCOF protection (when in parallel with mains) has
triggered.
Mains Vector Shift
Indicates that the Vector Shift protection (when in parallel with mains) has
triggered.
Maintenance Alarm 1,2,3 Due
Indicates that the specified maintenance alarm is due
Manual Mode
Active when the controller is in
MANUAL mode
Inactive in any other mode.
MSC Data Error
Indicates bad data transfer in the MultiSet Comms (MSC) Link
MSC Failure
Indicates that the number of sets on the MultiSet Comms (MSC) Link is lower
than it was previously.
MSC ID Error
Indicates that two or more modules connected on MultiSet Comms (MSC) Link
share the same MSC ID.
MSC Too Few Sets
Indicates that the number of sets connected on the MultiSet Comms (MSC)
Link is lower than the
Minimum sets required
setting.
Mute / Lamp test button pressed
This output indicates that the alarm mute / Lamp test push button is being
operated. Once the button is released, the output will become inactive.
Negative Phase Sequence Alarm
IEEE 37.2 - 46 phase balance current
relay
Active when the Negative Phase Sequence alarm is active
No Loading Command
This output indicates that the module is not calling for the
generator load switch to be closed. Should the module close the generator
load switch, this output will become inactive.
Oil Pressure Sender Open Circuit
Active when the
Oil Pressure Sensor
is detected as being
open circuit
.
Oil Pressure Switch
Active when a low oil pressure alarm is triggered by a low oil pressure switch
Open Generator Button Pressed
This output indicates that the Open Generator push button is being operated.
Once the button is released, the output will become inactive.
Open Gen Output
IEEE 37.2 – 52 ac circuit breaker
Used to control the load switching
device. Whenever the DSE module
selects the generator to be off load
this control source will be active.
Inactive whenever the generator is
required to be on load
Open Gen Output Pulse
IEEE 37.2 – 52 ac circuit breaker
Used to control the load switching device. Whenever the DSE module selects
the generator to be off load this control source will be active for the duration of
the Breaker Open Pulse timer, after which it will become inactive again.
Out of Sync
Indicates that the
out of sync
alarm has been triggered.
Summary of Contents for DSE8810
Page 126: ...Scada 126 5 8 2 POWER Shows the module measurements of the supply power ...
Page 134: ...Scada 134 5 12 STATUS Shows the module s current status ...
Page 144: ...Scada 144 5 19 COMMUNICATIONS INFORMATION Shows the module s communication ports settings ...
Page 146: ...Scada 146 5 20 1 DATA LOG STATUS Shows the memory status of the data log allocated space ...