4.4.2 COOLANT TEMPERATURE
4.4.2.1 COOLANT TEMPERATURE ALARMS
Options
Description
Pre alarm
= Pre-alarm is disabled
= If the temperature exceeds the
trip
setting, an alarm is generated. The temperature
must fall below the
return
setting to cease the alarm.
Electrical Trip
= Electrical trip is disabled
= If the temperature exceeds the
trip
setting, an alarm is generated, the load switch is
opened and the module enters the cooling timer after which the set is stopped.
Shutdown
If the temperature exceeds the
trip
setting, an alarm is generated, the load switch is opened
and the set is immediately stopped.
Click to edit the
‘sensor curve’. See
section entitled
Editing
the sensor curve
.
Select the
sensor type
Click and drag to
change the settings
Type the value or click the up and
down arrows to change the settings
Enable or disable the
alarms. The relevant
values below will appear
greyed out
if the alarm
is disabled.
An alarm will be
triggered if the sensor
is disconnected from
the module.
If an engine ECU is
selected, this instructs
the module to bypass
ECU data for oil
pressure reading.