DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
53
Engine settings – Crank disconnect
Value
Crank disconnect on generator frequency
21.0Hz
Crank disconnect oil pressure
<Disabled>
Check oil pressure prior to starting
Yes
Engine settings – speed
Value
Underspeed trip
#
1250 RPM
Disabled
Underspeed prealarm
#
1350 RPM
Disabled
Overspeed prealarm
#
1650 RPM
Disabled
Overspeed trip
#
1750 RPM
Disabled
Overspeed overshoot
#
0% Disabled
Plant battery settings
Trip
Return
Under volts warning
#
8.0V DC
9.0V DC
Over volts warning
#
33.0V DC
32.0V DC
Charge alternator warning
#
6.0V DC
N/A
Exercise scheduler settings
Value
Enable exercise scheduler
No
Comms
Value
Site identity
Genset ID
Modem mode
No modem
Modem init (not auto answer)
E0S7=60S0=0&S0&C1&D3
Modem init (auto answer)
E0S7=60S0=2&S0&C1&D3
Modem Hang
H0
Master inactivity timeout
5s
Slave ID
10 (Default)
Baud Rate
19200 (Default)
Languages
Value
Fixed Languages
#
English (UK)
User configured languages
Not used