DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
17
GENERATOR LOW VOLTAGE
if the module detects a generator output voltage below the below the pre-set trip
after the Safety On timer has expired, a shutdown is initiated. Alarm Shutdown Low Volts will be displayed.
Alarm
Shutdown
AC Undervolts
OIL PRESSURE SENDER OPEN CIRCUIT,
if the module detects a loss of signal from the oil pressure sender
(open circuit) a shutdown is initiated. Alarm Shutdown Sender Fault will be displayed. Sender failure is not delayed,
it is an
immediate shutdown
.
Alarm
Shutdown
Oil pressure
sender fault
AUXILIARY INPUTS
, if an auxiliary input has been configured as a shutdown the appropriate message will be
displayed as configured by the user.
Alarm
Shutdown
Bearing temp high
LOSS OF SPEED SIGNAL,
if the speed sensing signal is lost during cranking, a shutdown is initiated. Alarm
Shutdown Loss Of Speed Signal will be displayed.
Alarm
Shutdown
Loss of speed
signal
NOTE:- This will only occur if the speed sensing signal is lost during cranking or during the safety
on timer. If the signal is lost during normal operation the Generator will shutdown with an Under-speed
alarm.
CAN DATA FAIL
If the module is configured for CAN operation and does not detect data on the engine Can
datalink, a shutdown will occur and ‘Can data fail’ is shown on the module’s display.
Alarm
Shutdown
Can data fail