![Deep Sea Electronics Plc DSE5320 Operating Manual Download Page 39](http://html.mh-extra.com/html/deep-sea-electronics-plc/dse5320/dse5320_operating-manual_2463100039.webp)
DSE Model 5320 Automatic Mains Failure & Instrumentation System Operators Manual
Part No. 057-014 5320 OPERATING MANUAL ISSUE 5.1 18/06/2007 ADM
39
8.1.2 PLUG “B” 11 WAY
PIN
No
DESCRIPTION
CABLE
SIZE
NOTES
9
Charge fail / excite
2.5mm²
AWG 13
Do not connect to ground (battery –ve)
10
Auxiliary input 1
0.5mm²
AWG 20
Switch to Negative
11
Auxiliary input 2
0.5mm²
AWG 20
Switch to Negative
12
Auxiliary input 3
0.5mm²
AWG 20
Switch to Negative
13
Auxiliary input 4
0.5mm²
AWG 20
Switch to Negative
14
Auxiliary input 5
0.5mm²
AWG 20
Switch to Negative
15
Auxiliary input 6
0.5mm²
AWG 20
Switch to Negative
16 Functional
Earth
2.5mm²
AWG 13
Connect to a good clean earth point
17
Magnetic pickup Positive
0.5mm²
AWG 20
Connect to Magnetic Pickup device
18
Magnetic pickup Negative
0.5mm²
AWG 20
Connect to Magnetic Pickup device
19 Not
connected
-
NOTE:- Ensure magnetic pickup screen is connected to ground at one end only.
NOTE:- When the module is configured for CAN operation, terminals 17 & 18 should be left
unconnected. Engine speed is transmitted to the 53xx controller on the CAN link.
NOTE:- When the module is configured for CAN operation, FUEL, START and AUXILIARY output
requirements may be different. Refer to CAN and DSE Wiring for further information.