Measurement type
Unit
AWHP 4 MR
AWHP 6 MR-2
AWHP 8 MR-2
Acoustic power - Out
side
(1)
dB(A)
62.4
64.8
66.7
Refrigerant fluid
R410A
kg
2.1
2.1
3.2
Refrigerant connection
(Liquid - Gas)
inch
1/4 - 1/2
1/4 - 1/2
3/8 - 5/8
Max. pre-loaded length m
10
10
10
International protection
code (electrical)
IP X2D
IP X2D
IP X2D
(1) Noise radiated by the envelope - Test run in accordance with the NF EN 12102 standard, temperature conditions: air 7°C, water 55°C
3.2.3 Weight
Tab.16 Hydraulic module
Weight (empty)
kg
22
Note
For the weight of the boiler, refer to the Other Data table in the
Boiler technical characteristics section.
Tab.17 Outdoor unit
Weight (empty)
Unit
AWHP 4 MR
AWHP 6 MR-2
AWHP 8 MR-2
Outdoor unit
kg
42
42
75
3.2.4 Technical data - Low-temperature heat pump combination
heaters
Tab.18 Technical parameters for heat pump combination heaters (parameters declared for medium-temperature application)
Product name
AWHP 4MR–
EMC 24/28 MI
HYBRIDE
AWHP 6MR–
EMC 24/28 MI
HYBRIDE
AWHP 8MR–
EMC 24/28 MI
HYBRIDE
Air-to-water heat pump
Yes
Yes
Yes
Water-to-water heat pump
No
No
No
Brine-to-water heat pump
No
No
No
Low-temperature heat pump
No
No
No
Equipped with a supplementary heater
Yes
Yes
Yes
Heat pump combination heater
Yes
Yes
Yes
Rated heat output under average conditions
(1)
Prated
kW
6
8
11
Rated heat output under colder conditions
(1)
Prated
kW
5
6
9
Rated heat output under warmer conditions
(1)
Prated
kW
3
5
6
Declared capacity for heating for part load at in
door temperature 20 °C and outdoor temperature
T
j
T
j
= -7 °C
Pdh
kW
2.9
3.5
5.6
T
j
= +2 °C
Pdh
kW
3.5
4.5
6.1
T
j
= +7 °C
Pdh
kW
3.9
4.8
6.4
T
j
= +12 °C
Pdh
kW
4.8
5.2
6.5
T
j
= bivalent temperature
Pdh
kW
3.5
4.5
6.1
3 Technical specifications
7611444 - v02 - 11122015
17