5.1 ELECTRICAL CONNECTIONS FOR 24V MODELS
Execute the wiring following the directions of “Table 1” and diagrams on page 23.
WARNING
To ensure an appropriate level of electrical safety always keep the 230V power supply cables apart (minimum 4mm
in the open or 1 mm through insulation) from low voltage cables (motors power supply, controls, electric locks, aerial and auxiliary
circuits power supply), and fasten the latter with appropriate clamps near the terminal boards.
WARNING
Connect to the power supply 230 V ~± 10% 50 Hz through a multi pole switch or a different device that can ensure
multi pole disconnection from the power supply, with a contact opening of 3 mm.
WARNING
To connect the encoder to the control panel, use only a dedicated cable 3x0,22mm
2
.
Table 1 “terminal board connections”
1-2
+24 V
power supply output for auxiliary devices 200mA
3-4
22 V ~ transformer power supply input
5-6
24 V
battery power supply or photovoltaic accumulator Green Energy input (follow carefully polarity
indications).
7-8
Operator 1 output
9
Connection of motors metallic parts
10-11
Operator 2 output (if present)
12-13
24 V
max 15 W output for open gate fix/flashing warning light (if P052=0/1) or courtesy light (if P052>1)
14-15
14 (-)
“Boost” output for electric-lock, max 1 x art. 110 (if P062=0), 24V pulse output, max 5W (if P062=1),
step by step (if P062=2), electro-brake output for not self-locking operators (if P062=3), output for
electric-lock power supply via external relay (if P062=4), output for electro-magnets power supply for
barriers (ifP062=5) or temporized output (if P062>5).
15 (+)
16-17
24 V
Flashing light output max 15W art. Lumy/24A/S
18-19
18 - N.C.
Input 6 FCC 1. If it intervenes it stops M1 closing.
If unused, short circuit
.
If
the
installation
requires
different
comman
-
ds
and
/
or
add
itional
to
the
standard,
you
can
configure
each
input
to
the
required
rate.
R
efer to Chapter
“
Advanced Programming”.
19 - Com
20-21
20 - N.C.
Input 5 FCA 1. If it intervenes it stops M1 opening.
If unused, short circuit
.
21 - Com
22-23
22 - N.C.
Input 4 PHOTO 1. When enabled (see parameter P050 in the table), activation of
PHOTO 1 provokes: an inversion of direction (during closing), the arrest of the mo-
vement (during opening), prevent the start (gate closed).
If unused, short circuit
.
23 - Com
24-25
24 - N.C.
Input 3 SAFETY. If activated, it causes the inversion. See P055 and P056 on the para-
meters table.
If unused, short circuit
.
25 - Com
26-27
26 - N.O.
Input 2 PED. If activated, it opens motor nr. 1 only.
27 - Com
28-29
28 - N.O.
Input 1 START. In case of intervention it provokes: the operator opening or closing. It
may operate as “inversion” mode (P049=0) or “step by step” mode (P049=1).
29 - Com
30
Aerial signal input
31
Ground aerial input
32-33
32 (+)
DE@NET mains input (unused at the moment)
33 (-)
CON 1
230 V ~ ±10% (50/60 Hz) power supply input
J5
J9
Encoder selection Jumper:
•A position = operators with encoder (remind to set P029=0)
•B position = operators without encoder (remind to set P029=1)
A
B
A
B