DATALOGIC AUTOMATION - TH-TS series 

 

– INSTRUCTION MANUAL - Rev. 04 - PAGE 5

 

 

 

Examples with starts from values lower than SP and with decreasing 
of SP. 
 

4.9 - SOFT-START FUNCTION

 

All the parameters referring to the Soft -Start functioning are 
contained in the group 

]

rEG”.

 

The Soft-Start function only works through PID control and allows 
the limitation of control power when the instrument is switched on, for 
a programmable period of time. 
This is useful when the actuator, driven by the instrument, may be 
damaged excess power supplied when the application is not yet in 
the normal rating. (ex. for certain heating elements).  
The function depends on the following parameters : 

 “St.P”

 – Soft-Start power 

“Sst”

 – Soft-Start time (expressed in hh.mm) 

The possible function modes are the following : 

1) 

If both parameters are programmed with values other than OFF, 

when switched on the instrument gives an output power as 
programmed on par. “St.P” for the time programmed on par. “SSt”. 
Practically, the instrument works in manual condition and switches to 
automatic control at the elapsing of time “SSt”. 
It is advisable not to program a power “St.P” that is too high as the 
function is not deactivated when the automatic control power is 
found to be lower than the programmed one. 

2)

 If par. “St.P” = OFF and a value is set on par. “SSt” , at the switch 

on, the power calculated by the PID controller is divided by the time 
“SSt”, in order to calculate a ramp. The output power starts from 0 
and is progressively increased, depending on the calculated ramp, 
until the “SSt” time is reached or until the power overcomes the 
power calculated by the PID controller. 
To disable the Soft-Start function simply program par. “Sst” = OFF 
Whenever, a measurement errors occurs during the Soft-Start 
execution, the function is interrupted and the instrument gives an 
output power as programmed on par. “OPE”. 
If the measurement is restored, the Soft-Start is still deactivated. 
If it’s desired to activate the Autotuning with Soft-Start set par. 
“Auto”=4.  
The Autotuning will start automatically at the end of programmed 
Soft-Start cycle at the condition that the process value is lower (with 
“Func” =HEAt) than [SP- |SP/2|] or higher (with “Func” =CooL) than 
[SP+ |SP/2|]. 

 
4.10 – ALARM FUNCTIONING (AL1)

 

 

4.10.1 – ALARM OUTPUT CONFIGURATION

 

The alarm is depending on the process value (AL1) and before to set 
his functioning it’s necessary to establish to which output the alarm 
has to correspond to. 
First of all it’s necessary to configure, in the parameters group 

]

Out”, 

 the parameters relative to the outputs required as alarm 

(“O1F” , “O2F”) programming the parameter relative to the desired 
output as follows : 

= ALno

 if the alarm output has to be ON when the alarm is active, 

while it’s OFF when the alarm is not active 

= ALnc

 if the alarm output has to be ON when the alarm is not 

active, while it’s OFF when the alarm is active  

= ALni

 if the alarm output has to be ON when the alarm is not active, 

while it is OFF when the alarm is active but with reverse led 
indication (led ON= alarm OFF). 
Have now access at the group 

]

AL1”,

 and program on par. 

“OAL1”

 

, to which output the alarm signal has to be sent. 
The alarm functioning is instead defined by parameters : 

"AL1t "

 – ALARM TYPE 

"Ab1"

 – ALARM CONFIGURATION 

“AL1”

 – ALARM THRESHOLD  

“AL1L”

 – LOW ALARM THRESHOLD (for band alarm) OR 

MINIMUM SET OF AL1 ALARM THRESHOLD (for low or high 
alarm) 

“AL1H”

 - HIGH ALARM THRESHOLD (for band alarm) OR 

MAXIMUM SET OF AL1 ALARM THRESHOLD (for low or high 
alarm) 

“HAL1” - 

ALARM HYSTERESIS 

“AL1d”

 – ALARM ACTIVATION DELAY (in sec.) 

"AL1i"

 – ALARM BEHAVIOUR IN THE EVENT OF 

MEASUREMENT ERROR 

"AL1t" – ALARM TYPE :

  the alarm output can behave in six 

different ways.

 

LoAb = ABSOLUTE LOW ALARM: The alarm is activated when the 
process value goes below the alarm threshold set on parameter 
"AL1”. With this mode is possible to program the minimum and the 
maximum set  of  “AL1” by “AL1L” and “AL1H” parameters.

 

 

HiAb = ABSOLUTE HIGH ALARM: The alarm is activated when the 
process value goes higher than the alarm threshold  set on 
parameter "AL1". With this mode is possible to program the 
minimum and the maximum set  of  “AL1” by “AL1L” and “AL1H” 
parameters. 

 

LHAb = ABSOLUTE BAND ALARM: The alarm is activated when the 
process value goes under the alarm threshold set on parameter 
"AL1L" or goes higher than the alarm threshold set on parameter 
"AL1H". 

 

LodE = DEVIATION LOW ALARM: The alarm is activated when the 
process value goes below the value [SP + AL1]. With this mode is 
possible to program the minimum and the maximum set  of  “AL1” by 
“AL1L” and “AL1H” parameters. 

 

HidE = DEVIATION HIGH ALARM: The alarm is activated when the 
process value goes above the value [SP + AL1]. With this mode is 
possible to program the minimum and the maximum set  of  “AL1” by 
“AL1L” and “AL1H” parameters. 

 

LHdE = DEVIATION BAND ALARM: The alarm is activated when the 
process value goes below the value [SP + AL1L] or goes above than 
the value [SP + AL1H] 

Summary of Contents for TH Series

Page 1: ...le to exit by the fast programming mode or it is possible to visualise the alarm thresholds see par 2 3 To exit the fast Set programming it is necessary to push key P after the visualisation of the last Set Point or alternatively if no key is pressed for approx 15 seconds the display will return to normal functioning automatically 2 2 SELECTION OF THE CONTROL STATE AND PARAMETER PROGRAMMING By pus...

Page 2: ... the power supply to the equipment It is also recommended that all the electrical circuits connected to the instrument must be protect properly using devices ex fuses proportionate to the circulating currents It is strongly recommended that cables with proper insulation according to the working voltages and temperatures be used Furthermore the input cable of the probe has to be kept separate from ...

Page 3: ...par Cont nr The Neutral Zone control is used to control plants in which there is an element which causes a positive increase ex Heater humidifier etc and an element which causes a negative increase ex Cooler de humidifier etc The control functions works on the programmed outputs depending on the measurement on the active Set Point SP and on the hysteresis HSEt The control works in the following wa...

Page 4: ...the connected plant in order to calculate the most suitable PID parameters If Auto 1 or Auto 2 and if at the Auto tuning start the condition for the lower process value is not found with Func HEAt than SP SP 2 or higher with Func CooL than SP SP 2 the display will show ErAt and the instrument will be swapped to normal control conditions according to the previously programmed parameters To make the...

Page 5: ...re to set his functioning it s necessary to establish to which output the alarm has to correspond to First of all it s necessary to configure in the parameters group Out the parameters relative to the outputs required as alarm O1F O2F programming the parameter relative to the desired output as follows ALno if the alarm output has to be ON when the alarm is active while it s OFF when the alarm is n...

Page 6: ...ble to the low threshold AL1L while the example of the high alarm is applicable to the high threshold AL1H 4 11 LOOP BREAK ALARM FUNCTION All the parameters referring to the Loop Break alarm function are contained in the group LbA The Loop Break alarm is available on all the instruments which intervenes when for any reason short circuit of a thermocouple thermocouple inversion load interruption th...

Page 7: ...HAb LodE HidE LHdE HiAb OPER 23 Ab1 Alarm AL1 functioning 0 15 0 CONF 24 AL1 Alarm AL1 threshold AL1L AL1H 0 OPER 25 AL1L Low threshold band alarm AL1 or Minimum set alarm AL1 for high or low alarm 1999 AL1H 1999 CONF 26 AL1H High threshold band alarm AL1 or Maximum set alarm AL1 for high or low alarm AL1L 9999 9999 CONF 27 HAL1 Alarm AL1 hysteresis OFF 9999 1 CONF 28 AL1d Activation delay of alar...

Page 8: ...ed value InE OPE FUNCTIONING IN CASE OF MEASUREMENT ERROR This defines the error conditions of the input allowing the instrument to give the power programmed on par OPE as output The possibilities are Or the condition occurs in case of over range or probe breakage Ur the condition occurs in case of under range or probe breakage Our the condition occurs in case of over range or under range or probe...

Page 9: ...tion 4 if it s desired to activate the autotuning automatically at the end of programmed Soft Start cycle The Autotuning will start at the condition that the process value is lower with Func HEAt than SP SP 2 or higher with Func CooL than SP SP 2 OFF Autotuning disabled When it s occurring an Autotuning cycle led AT blinks SELF SELF TUNING ENABLE Parameter used to enable yES or disable no the Self...

Page 10: ...ry to repeat the auto tuning LbA Loop control interrupted Loop break alarm Check the working of probe and actuator and swap the instrument to rEG control ErEP Possible anomaly of the EEPROM memory Push key P In error conditions the instrument provides an output power as programmed on par OPE and activates the desired alarms if the relative parameters ALni have been programmed yES 6 2 CLEANING We r...

Page 11: ... 55 0 150 0 C 67 0 302 0 F NTC 103 AT2 SEnS ntc 50 110 C 58 230 F 50 0 110 0 C 58 0 230 0 F 7 5 MECHANICAL DIMENSIONS PANEL CUT OUT AND MOUNTING mm THT Series For any further information please contact DATALOGIC AUTOMATION Via Lavino 265 40050 Monte S Pietro Bologna Italy Tel 39 051 6765611 Fax 39 051 6759324 www automation datalogic com e mail info automation datalogic com Datalogic and the Datal...

Reviews: