       All safety related  codifications, symbols and instructions that appear in this operating manual 
or on the equipment must be strictly followed to ensure the safety of the operating personnel as 
well as the instrument. 

      If all the equipment is not handled in a manner specified by the manufacturer, it might impair the 
protection provided by the equipment .

Product improvement and upgrade is a constant procedure. So for more updated operating information and support, 
Please contact our helpline : +91-9978991474/76/82 or Email at [email protected]             Ver: 01-2017

=>

 Read complete instructions prior to installation and operation of the unit. 

WARNING

 : Risk of electric shock.

 3)  Cable used for connection to power source, must have a cross section of 1mm or greater. These wires 
       should have insulations capacity made of at least 1.5kV.      

 2) To reduce electro magnetic interference, use wire with adequate rating and twists of the same of equal size shall 
      be made with shortest connection.            

 4)  When extending the thermocouple lead wires, always use thermocouple compensation wires for wiring for the RTD
       type, use a wiring material with a small lead resistance (5

Ω

 max per line)and no resistance differentials among  

       three wires should be present.        

 1) To prevent the risk of electric shock power supply to the equipment must be kept OFF while doing the wiring 
      arrangement. Do not touch the terminals while power is being supplied.  

 5)  A better anti-noise effect can be expected by using standard power supply cable for the instrument.         

1) This equipment, being built-in-type, normally becomes a part of main control panel and such in case the 
    terminals do not remain accessible to the end user after installation and internal wiring.  

2) Do not allow pieces of metal, wire clippings, or fine metallic fillings from installation to enter the product 
     or else it may lead to a safety hazard that may in turn endanger life or cause electrical shock to the operator.      
3) Circuit  breaker or mains switch must be installed between power source and supply terminal to 
    facilitate power ‘ON’ or ‘OFF’ function. However this mains switch or circuit breaker must be 
     installed at convenient place normally accessible to the operator.     
4) Use and store the instrument within the specified ambient temperature and humidity ranges as 
     mentioned in this manual.     

Warning Guidelines

Safety Precautions

Installation Guidelines

Mechanical Installation

Maintenance

1) Prepare the panel cutout with proper dimensions as show above.
2) Fit the unit into the panel with the help of clamp given.
3) The equipment in its installed state must not come in close proximity to any heating source, 
    caustic vapors, oils steam, or other unwanted process by products.
4) Use the specified size of crimp terminal (M3.5 screws) to wire the terminal block. Tightening the
     screws on the terminal block using the tightening torque of the range of 1.2 N.m.
5) Do not connect anything to unused terminals. 
   

1) The equipment should be cleaned regularly to avoid blockage of ventilating parts.         

2) Clean the equipment with a clean soft cloth. Do not use isopropyl alcohol or any other cleaning agent.
3) Fusible resistor must not be replaced by operator. 

2

UTC-113P,213P,413P

95mm  -  3.75 inches

85mm  -  3.34 inches

68mm  -  2.68 inches

60mm  -  2.36 inches

136mm  -  5.35 inches

120mm  -  4.72 inches

B

A

C

C

C

D

D

D

F

E

F

E

MODEL

A

96mm

96mm

92mm

92mm

3mm

50mm

B

C

D

E

F

DIMENSIONS

MODEL

A

72mm

72mm

68mm

68mm

3mm

85mm

B

C

D

E

F

DIMENSIONS

MODEL

A

48mm

48mm

44mm

44mm

3mm

95mm

B

C

D

E

F

DIMENSIONS

B

A

1 2 3

UTC 413P

UTC 113P

R

PV

ºC

1 2 3

B

A

R

PV

TUNE

SET

ºC

UTC 213P

1 2 3

E

F

TC

+

-

+

SSR

O/P

RTD

6

7

8

9

10

-

1

2

3

4

5

NC

C

R1

NO

L

!

100  
250V AC
    

50/60 HZ
4VA

~

 

!

100  
270V AC
    

50/60 Hz
4VA

~

 

TC

+

RTD

-

!

L

N

1

2

3

4

5

6

7

-

+

O/P

S.S.R

 RELAY1

100  
270V AC
    

~

 

50/60 Hz
4VA

NC

NO

C

8

9

10

11

12

13

14

1

7

8

9

12

13

14

10

11

16

17

18

19

20

15

2

3

4

5

6

NC

C

NO

TC

+

-

+

-

RELAY

 

100 
270V AC

~

 

50/60 Hz
4VA

!

L

N

O/P

S.S.R

RTD

www.multispanindia.com

Page - 1

UTC-113P,213P,413P

Note:

 1)

 

If Sensor Connection is reversed, Display will show “

SRE

” message.

 2) If Sensor is not connected, Display will show 

Opn

 message.

 3) Every time the instrument is turned ON, Following pattern will be displayed

              J: 0 to 600°C / K: 0 to 999°C / 
                       PT-100: -99 to 400ºC

PID / ON-OFF (selectable)

Output 

 Power Supply

 Protection Level

    Operating

    Relative

 (As per request)

 Temperature

   Humidity

          1 relay, 1 C/O contact, 230V AC, 5A ; 1 SSR,12V DC Approx, 30mA DC

100 to 270V AC, 50 / 60 Hz, Approx 4VA 

IP-65(Front side) AS per IS/IEC 60529:2001

0°C To 55°C

Up to 95% RH Non Condensing

Model

Display

Size(HXWXD)
Panel Cutout

Input

Temperature 
      Range

Control Action

UTC 113P

96 X 96 X 50 mm

68 X 68 mm

92 X 92 mm

44 X 44 mm

72 X 72 X 85 mm

48 X 48 X 95 mm

3 Digit 7 seg 0.56”,red LED Display

UTC 213P

UTC 413P

 J, K, PT-100 (selectable) 

Technical Specification  

Connection Diagram  

OPERATING MANUAL 

PID TEMPERATURE CONTROLLER                           

UTC-113P, 213P & 413P

1 2 3

UTC 413P

POWER ON

All digit segment will be turned ON for 3 sec 

Previous or default sensor input will be display for 2 sec

Process Value

8 8

8

- J -

1 2 3

UTC 113P

R

PV

ºC

1 2 3

R

PV

TUNE

SET

ºC

UTC 213P

1 2 3

N

Made in India