background image

DATALOGIC AUTOMATION - TH-TS series 

 

– INSTRUCTION MANUAL - Rev. 04 - PAGE 4

 

 

Please remember that a low value on this parameter reduces the 
overshoot while a high value increase it. 

 

1: Value “FuOC” OK 
2: Value “FuOC” too high 
3: Value “FuOC” too low 
 

4.6 - DOUBLE ACTION PID CONTROL (1rEG - 2rEG) 

All the parameters referring to PID control are contained in the group 

]

rEG”. 

The Double Action PID control is used to control plants where there 
is an element which causes a positive increase (ex. Heating) and an 
element which causes a negative increase (ex. Cooling). 
This type of control can be obtained when 2 outputs are 
programmed respectively as 1rEG and 2rEG and the par. 

“Cont”

 = 

Pid. 
The element causing a positive increase has to be connected to the 
output programmed as 1rEG while the element causing a negative 
increase has to be connected to the output programmed as 2rEG. 
The Double Action PID control works on the outputs 1rEG and 2rEG 
depending on the active Set Point 

“SP” 

and on the instrument’s PID 

algorithm with two degrees of freedom. 
In order to obtain good stability of the process variable, in case of 
fast processes, the cycle times “tcr1” and “tcr2” have to have a low 
value with a very frequent intervention of the control outputs. 
In this case  use of solid state relays (SSR) to drive the actuators is 
recommended. 
The Double Action PID control algorithm needs the programming of 
the following parameters : 

"Pb"

 – Proportional Band 

"tcr1"

 – Cycle time of the output 1rEG 

“tcr 2”

 – Cycle time of the output 2rEG 

"Int"

 – Integral Time 

"rS"

 – Manual Reset (if “Int =0 only) 

"dEr"

 – Derivative Time 

“FuOC” - 

Fuzzy Overshoot Control

 

"Prat"

 - Power Ratio or relation between power of the element 

controlled by output 2rEG and power of the element controlled by 
output 1rEG. If par. “Prat” = 0, the output 2rEG is disabled and the 
control behaves exactly as a single action PID controller, through 
output 1rEG. 
 

4.7 - AUTOTUNING

 

AND SELFTUNING FUNCTIONS

 

All the parameters referring to the AUTOTUNING and SELFTUNING 
functions are contained in the group 

]

rEG”. 

The AUTOTUNING and SELFTUNING functions permit the 
automatic tuning of the PID controller. 
The 

AUTOTUNING

 function permits the calculation of the PID 

parameters by means of a FAST type tuning cycle and, at the end of 
this operation, the parameters are stored into the instrument’s 
memory and remain constant during control. 
The 

SELFTUNING

 function (rule based "TUNE-IN") instead allows 

control monitoring and the continuous calculation of the parameters 
during control. 
Both functions automatically calculate the following parameters : 

"Pb"

 – Proportional Band 

"tcr1"

 – Cycle time of the output 1rEG 

"Int"

 – Integral Time 

"dEr"

 – Derivative Time 

“FuOC” - 

Fuzzy Overshoot Control

 

and, for the Double Action PID control, also : 

“tcr 2”

 – Cycle time of the output 2rEG 

"Prat"

 - Ratio P 2rEG/ P 1rEG 

To activate the AUTOTUNING function proceed as follows : 
Press the T pushbutton, at this point the Auto-tuning function is 
activated and is indicated by the flashing led AT/ST. 
The regulator carries out several operations on the connected plant  
in order to calculate the most suitable PID parameters.   
If “Auto” = 1 or “Auto” = 2, and if, at the Auto-tuning start, the 
condition for the lower process value is not found (with “Func” 
=HEAt) than [SP- |SP/2|] or higher (with “Func” =CooL) than [SP+ 
|SP/2|], the display will show 

“ErAt”

 and the instrument will be 

swapped to normal control conditions according to the previously 
programmed parameters. 
To make the error “ErAt” disappear, swap the instrument to the OFF 
control (OFF) and then turn it to automatic control (rEG). 
The Autotuning cycle duration has been limited to 12 hours 
maximum. 
If Auto-tuning is not completed within 12 hours, the instrument will 
show 

"noAt" 

on the display

.

  

In case of probe error, the instrument automatically stops the cycle in 
progress. 
The values calculated by Auto-tuning are automatically stored in the 
instrument’s memory at the end of the correct PID parameters 
tuning.  

Note :

 The instrument is already programmed in our factory to carry 

out autotuning at every instrument switch on ("Auto" = 1). 
To activate the SELFTUNING function proceed as follows 
1) Program par. 

"SELF"

 = yES 

2) Exit from the parameter programming. 
3) Connect the instrument to the controlled plant. 
4) Activate Self-tuning selecting par. 

“tunE”

 in the main menu (or by 

correctly programming key “U”). 
When the Self-tuning function is active, the led AT/ST is permanently 
lit up and all the PID parameters ("Pb", "Int", "dEr", etc.) are no 
longer visualized. 
 

4.8 - REACHING OF THE SET POINT AT CONTROLLED SPEED 
AND AUTOMATIC SWITCHING BETWEEN TWO SET POINTS 
(RISE RAMP, FALL RAMP AND DWELL TIME)

 

All the parameters referring to the ramps functioning are contained in 
the group 

]

rEG”.

 

It is possible to reach the set point in a predetermined time (in any 
case longer than the time the plant would naturally need). This could 
be useful in those processes (heating or chemical treatments, etc.) 
where the set point has to be reached gradually, in a predetermined 
time. 
Once the instrument has reached the first Set Point (SP1) it is 
possible to have automatic switching to the second Set Point (SP2) 
after a set time, thus obtaining a simple automatic thermic cycle. 
These functions are available for all the programmable controls (PID 
single and double action, ON/OFF and Neutral Zone ON/OFF). 
The function is determined by the following parameters :  

"SLor"

 - Gradient of rise ramp  (Process value < Set point) 

expressed in unit/minute  

"SLoF"

 - Gradient of fall ramp (Process value > Set point) 

expressed in unit/minute. 

"dur.t"

 – Dwell time of Set Point SP1 before automatic switching to 

Set Point 2 SP2 (expressed in hrs. and min.). 
The functions are deactivated when the relative parameters are = 
InF. 
When the Set Point value is changed or at switch on, the instrument 
automatically determines which of the two values “SLor” or “SLoF” it 
has to use.  

Note:

 In case of PID control, if Auto-tuning is desired whilst the ramp 

function is active, this will not be carried out until the tuning cycle has 
been completed. 
It is therefore recommended that Auto-tuning be started avoiding 
activating the ramp function and, once the tuning is finished, 
deactivate Auto-tuning  (“Auto” = OFF), program the desired ramps 
and, if it automatic tuning is desired, enable the Self-tuning function. 

Summary of Contents for TH Series

Page 1: ...le to exit by the fast programming mode or it is possible to visualise the alarm thresholds see par 2 3 To exit the fast Set programming it is necessary to push key P after the visualisation of the last Set Point or alternatively if no key is pressed for approx 15 seconds the display will return to normal functioning automatically 2 2 SELECTION OF THE CONTROL STATE AND PARAMETER PROGRAMMING By pus...

Page 2: ... the power supply to the equipment It is also recommended that all the electrical circuits connected to the instrument must be protect properly using devices ex fuses proportionate to the circulating currents It is strongly recommended that cables with proper insulation according to the working voltages and temperatures be used Furthermore the input cable of the probe has to be kept separate from ...

Page 3: ...par Cont nr The Neutral Zone control is used to control plants in which there is an element which causes a positive increase ex Heater humidifier etc and an element which causes a negative increase ex Cooler de humidifier etc The control functions works on the programmed outputs depending on the measurement on the active Set Point SP and on the hysteresis HSEt The control works in the following wa...

Page 4: ...the connected plant in order to calculate the most suitable PID parameters If Auto 1 or Auto 2 and if at the Auto tuning start the condition for the lower process value is not found with Func HEAt than SP SP 2 or higher with Func CooL than SP SP 2 the display will show ErAt and the instrument will be swapped to normal control conditions according to the previously programmed parameters To make the...

Page 5: ...re to set his functioning it s necessary to establish to which output the alarm has to correspond to First of all it s necessary to configure in the parameters group Out the parameters relative to the outputs required as alarm O1F O2F programming the parameter relative to the desired output as follows ALno if the alarm output has to be ON when the alarm is active while it s OFF when the alarm is n...

Page 6: ...ble to the low threshold AL1L while the example of the high alarm is applicable to the high threshold AL1H 4 11 LOOP BREAK ALARM FUNCTION All the parameters referring to the Loop Break alarm function are contained in the group LbA The Loop Break alarm is available on all the instruments which intervenes when for any reason short circuit of a thermocouple thermocouple inversion load interruption th...

Page 7: ...HAb LodE HidE LHdE HiAb OPER 23 Ab1 Alarm AL1 functioning 0 15 0 CONF 24 AL1 Alarm AL1 threshold AL1L AL1H 0 OPER 25 AL1L Low threshold band alarm AL1 or Minimum set alarm AL1 for high or low alarm 1999 AL1H 1999 CONF 26 AL1H High threshold band alarm AL1 or Maximum set alarm AL1 for high or low alarm AL1L 9999 9999 CONF 27 HAL1 Alarm AL1 hysteresis OFF 9999 1 CONF 28 AL1d Activation delay of alar...

Page 8: ...ed value InE OPE FUNCTIONING IN CASE OF MEASUREMENT ERROR This defines the error conditions of the input allowing the instrument to give the power programmed on par OPE as output The possibilities are Or the condition occurs in case of over range or probe breakage Ur the condition occurs in case of under range or probe breakage Our the condition occurs in case of over range or under range or probe...

Page 9: ...tion 4 if it s desired to activate the autotuning automatically at the end of programmed Soft Start cycle The Autotuning will start at the condition that the process value is lower with Func HEAt than SP SP 2 or higher with Func CooL than SP SP 2 OFF Autotuning disabled When it s occurring an Autotuning cycle led AT blinks SELF SELF TUNING ENABLE Parameter used to enable yES or disable no the Self...

Page 10: ...ry to repeat the auto tuning LbA Loop control interrupted Loop break alarm Check the working of probe and actuator and swap the instrument to rEG control ErEP Possible anomaly of the EEPROM memory Push key P In error conditions the instrument provides an output power as programmed on par OPE and activates the desired alarms if the relative parameters ALni have been programmed yES 6 2 CLEANING We r...

Page 11: ... 55 0 150 0 C 67 0 302 0 F NTC 103 AT2 SEnS ntc 50 110 C 58 230 F 50 0 110 0 C 58 0 230 0 F 7 5 MECHANICAL DIMENSIONS PANEL CUT OUT AND MOUNTING mm THT Series For any further information please contact DATALOGIC AUTOMATION Via Lavino 265 40050 Monte S Pietro Bologna Italy Tel 39 051 6765611 Fax 39 051 6759324 www automation datalogic com e mail info automation datalogic com Datalogic and the Datal...

Reviews: