40
Temporal diagram of the Muting function for four-
sensor configuration (“T-shaped” version)
MUTING1
0Vdc
24Vdc
t
AB
MUTING2
MUTING STATUS
0Vdc
24Vdc
OFF
(ESPE normal
operation)
ON
As shown in the previous picture, t
AB
indicates the interval of time between MUTING1 and MUTING2
activation (see paragraph 6.6.4 - "Installation mode of Muting sensors
”). In this case, when MUTING1 de-
activates, light curtain exits the muting status and returns in normal operation.
6.6.2 Muting timeout selection function
This function let the user choose the muting timeout value between 10 minutes and infinite and can be set by
dip-switches of RX device (see section 5
– “ELECTRICAL CONNECTIONS AND CONFIGURATION”).
6.6.3 Muting low-pass filter function
The muting filter is a filter on the muting inputs; low-high or high-low transitions of MUTINGs signals are
considered valid only if maintained for t
F
seconds (t
F
≥ 0.1 s), as shown in the following figure.
MUTINGx line
0Vdc
24Vdc
t
F
MUTINGx line active
OFF
ON
t
F
This function can be enabled using dip-switches of RX device (see section 5