gForce Ultra IOM
25
Table 5 Liquid Lines (Dual Circuit Systems)
Unit kW
Equivalent Feet (Meters)
50 (15.2)
100 (30.5)
150 (45.7)
200 (61.0)
70
7
/8”
7
/8”
7
/8”
7
/8”
91
7/8”
7/8”
7/8”
7/8”
125
1-1/8
”
1-1/8
”
1-1/8
”
1-1/8
”
NOTE:
1. If equivalent piping length falls between two columns above, choose
the longer equivalent length.
2. Dual circuit units should use the same line size on both circuits.
3. If hot gas line
refrigerant flow is upward, use “Vertical Up”.
4. If hot gas line refrigerant flow
is downward, use “Horizontal & Vertical
Down
”.
Connection Sizes, Air-cooled Units
Table 6 Air-cooled Units Connection Sizes
Model Number
Liquid Line
Hot Gas Line
GUA* 022
5/8” (16 mm) O.D.
5/8” (16 mm) O.D.
GUA* 036
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
GUA* 045
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
GUA* 070
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
GUA* 091
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
GUA* 125
1-
1/8” (29 mm) O.D.
7/8” (22 mm) O.D.
* Indicates D = Downflow and U = Upflow Configuration
NOTE:
Field connections at the indoor evaporator and remote
condenser will not necessarily be the same as the field pipe size required.