gForce Ultra IOM
91
dap4 Settings for Ultra Units
q.
Number of Fans:
Fan K-Factor:
Minimum Flow:
Maximum Flow:
Set Point:
One
(Default)
348
(Default)
2000 CFM (Default)
32000 CFM (Default)
15000 CFM (Default)
r.
Fan Flow Tuning PID -
This screen will display if Display Airflow is selected
Status:
Setpoint:
Integration Time:
Band Per Fan:
Deviation Time:
Current Demand:
00 CFM
(Reading, not a setting)
15000 CFM
5S
666 CFM
1s
40%
5.
Menu K - Alarms & Limits
a.
Alarm Setting:
Audio Mode:
Pwr-Up:
EVD Alm Shutdown:
Maint Due Msg:
Stdby Alms Active:
None (Default)
Auto, No Alarm (Default)
Yes (Default)
None (Default)
No (Default)
b.
Alarm Settings:
Comp Short Cycle:
Floor Water Alarm Action:
Reset Alarm Log:
Alarm Screen Contact:
Yes (Default)
Alarm Only (Default)
No (Default)
No Contact Message (Default)
c.
Flow Alarms:
No Water Flow Action:
Wtr Flow Alm Dly:
Air Flow Dly:
Alarm Only (Default)
5s (Default)
5s (Default)
d.
Return Air Alarms:
Firestat Setpoint:
Hi Temp Alarm:
Set Point:
Lo Temp Alarm:
Set Point:
150
F (Default)
Yes (Default)
80
F (Default)
Yes (Default)
60
F (Default)
e.
Opt Temp Alarms:
Low Disch Temp Alm:
Shut Off Comps:
Set Point:
Yes (Default)
No (Default)
45.0
F
f.
Humidity Alarms:
HI Humidity Alarm:
Set Point:
Lo Humidity Alarm:
Set Point:
Yes (Default)
60% (Default)
Yes (Default)
40% (Default)
g.
Freeze Alarm:
Freeze-Stat Alarm: No (Default)
h.
EEV Alarms:
Shutdown Comps:
Hi Superheat Delay:
Yes (Default)
90s (Default)