![Data Aire dap4 touch User Manual Download Page 90](http://html1.mh-extra.com/html/data-aire/dap4-touch/dap4-touch_user-manual_3604236090.webp)
86
MENU M
– Set Zone Control (continued)
Zone Control Schedule
Current Cfg:
Primary
Override Active:
No
Override Time:
4 Hrs
This screen will only appear when the secondary schedule is used.
Current Cfg:
shows which schedule is currently running. (Primary or
Secondary).
Override Active: (only shown when secondary schedule is running
)
Allows you to override the secondary schedule to run the primary
schedule.
Override Time:
is the setting for how many hours the override will last.
Range of adjustment is 1 to 12 hours, with a default of 4 hours.
Zone Weekday Schedule
Day: Monday
Copy to: Tuesday
No
Setting
1: 08:00
Primary
2: 17:00
Secondary
3: 23:00
------
4: 01:00
------
Note: The times displayed on the scheduler screens are in military (24
hour) format. Example; 6:00 PM = 18:00).
Day
–
This is the selection of the weekday that you are currently
configuring.
Copy to -
This selection allows you to copy the settings of the day currently
being displayed to another day without going through settings routine for
each day. The field to the right of this selection causes the copy to take
place by changing
“ No” to “Yes”. A message “Successful Copy” will then be
momentarily displayed.
Time and Setting
–
Set the time of day when the schedules should
change. Then set which schedule should be run at the time selected:
Primary or Secondary.
When the clock reaches the time set, the schedule switches to the one
selected. Under normal circumstances, each time setting would have the
opposite schedule of the previous one. The schedules can be switched up
to four times a day. Leave blank (----) if no additional scheduling is required.
Summary of Contents for dap4 touch
Page 1: ...1 dap4 User Manual Data Aire Inc 230 W BlueRidge Avenue Orange CA 92865 www dataaire com...
Page 33: ...32 MENU F INFORMATION differently from what is written in this manual...
Page 69: ...66 MENU K ALARMS LIMITS Service Level continued Control Only...
Page 82: ...78...
Page 133: ...129 Wiring Connections...