Changing the Passwords
Important Notice
– Service and Factory level passwords should only
be given to qualified technicians. Under normal circumstances the
Factory menus should not be changed. Please consult with Data Aire
engineering or service personnel for help using these menus.
Change the Service level and Factory level passwords following these steps:
1. Press the Menu key.
2. Enter the current Service Level or Factory Level password.
3. The Main Menu will appear. Press the Menu key
4. The password screen will appear. Press the DOWN key.
5. A Service Security screen will appear. Choose a new service level
password. Note: if the Factory level password was entered on step 2; press
the DOWN key again to be able to change the Factory level password.
Note: Be sure you write down any changes to these passwords and store in a safe
and secure location.
MENU A
–
ON / OFF
On / Off Unit
Start-up Delay: 5s
Start-up Mode: Off
Status: OFFbyKEY
Hold ESC for 5 seconds
to turn unit ON or OFF
Start-up Delay:
This is the amount of time that the control will wait before starting.
It is often used to prevent multiple units from starting at the same time, which may
cause a surge in power. Selection is from 5 to 600 seconds with a default setting of
5 seconds. A count down timer for this delay is shown on the main status screen.
Startup- Mode:
This is the mode that the unit will be in when power is applied.
Selection is either On or Off with a default setting of Off.
Note: When startup mode
is set to Off, the Esc key must be used in order to turn the unit on.
Status:
Shows the current unit status as displayed on the main status screen.
Summary of Contents for dap4 touch
Page 1: ...1 dap4 User Manual Data Aire Inc 230 W BlueRidge Avenue Orange CA 92865 www dataaire com...
Page 33: ...32 MENU F INFORMATION differently from what is written in this manual...
Page 69: ...66 MENU K ALARMS LIMITS Service Level continued Control Only...
Page 82: ...78...
Page 133: ...129 Wiring Connections...