59
MENU J
– FACTORY SETTINGS (factory level) continued
Damper Status:
This line will indicate
“OK- Modulating” when the Airside
Economizer is available to perform cooling. Otherwise, it will state what condition is
preventing it from running.
Damper Modulation:
Shows the current damper modulation based on
temperature demand.
Min Damper Open:
This setting determines the minimum opening of the damper.
Range of selection is 0 to 70% with a default setting of 0%.
Max Damper Open:
This setting determines the maximum opening of the damper.
Range of selection is 70% to 100% with a default setting of 100%.
Rack Settings
Temp Sensors Used: 32
Groups Used:
16
Exclude T Band:
10.0
Use Average of Groups
Avg: Highest 3 Groups
Refresh Rate:
15min
Offset Setpoint:
No
Temp Sensors Used:
Select how many rack sensors are installed. Range of
selection is 0 (default) to the maximum sensors supported by the module. Note: An
external rack sensor module is required when more than 1 sensor is selected (3
sensors on IRDX and IRCW models). Use the Options Installed screen to select
the type of external module installed.
Groups Used:
(only shown when 4 or more temp sensors are installed). This is
the total number of groups that the sensors will be arranged in. Range of
adjustment is: None (default setting) to ½ the number of temp sensors installed.
When groups are not used, all sensors are effectively in the same group.
Exclude T Band:
(only shown when external module is installed). This is the
amount of deviation from the average rack temperature. If a sensor deviates more
that this setting, it will be excluded from control and determining the average
temperature. Once it comes back within the exclude T band for at least 60
seconds, it will return to normal function. Range of adjustment is 5.0
°F
to 99.0
°F
with a default setting of 10.0
°F
Use Highest:
The rack temperature can be determined by using the Highest or the
Average temperature of sensors or groups of sensors.
Summary of Contents for dap4 touch
Page 1: ...1 dap4 User Manual Data Aire Inc 230 W BlueRidge Avenue Orange CA 92865 www dataaire com...
Page 33: ...32 MENU F INFORMATION differently from what is written in this manual...
Page 69: ...66 MENU K ALARMS LIMITS Service Level continued Control Only...
Page 82: ...78...
Page 133: ...129 Wiring Connections...