41
MENU J
– FACTORY SETTINGS (factory level) continued
Static Air
Pressure
Set Point: 2.500"Wtr
Band: "Wtr
Int Time: 300s
Note: The Static Air Pressure (or Differential Air pressure) screen is only displayed
when CW or DX fan mode is set to modulate to maintain Air Pressure.
The dap4 uses a proportional integral algorithm (P+I) to maintain air pressure. The
description of the settings offered below is only a guide. The difference between
the set point and the actual measured air pressure is called the error.
Set Point:
The pressure (in inches or water coulomb) that the fan speed will
modulate to maintain. Range of adjustment is 0.001 to 9.999
” Wtr with a default
setting of 0.500
”Wtr.
Band:
This setting is effectively the
“sensitivity” of the algorithm. The smaller the
band, the more the algorithm will try to correct the error. If the band setting is too
low, the system will oscillate by being over-responsive. If the band setting is
too high, fan speed may lack responsiveness. Ideally, the band s et t ing
s hou ld be as lo w a s possible without causing oscillation. Range of adjustment
is 0 to 32767cfm with a default of 666cfm.
Integration Time:
Used to slowly shift the fan speed level as a result of an error
between set point and t h e measured a i r p r e s s u r e . The h i g h e r Integral time
setting, the slower the f a n s p e e d level will be shifted. If the Integral time is set
too low the f a n s p e e d could c h a n g e quickly, causing oscillation. If Integral
time s e tti n g is too h i g h , fan speed may become sluggish to change. A
setting of 0s (default) puts the algorithm in a proportional only mode. Range of
adjustment is 0 to 999s.
Summary of Contents for dap4 touch
Page 1: ...1 dap4 User Manual Data Aire Inc 230 W BlueRidge Avenue Orange CA 92865 www dataaire com...
Page 33: ...32 MENU F INFORMATION differently from what is written in this manual...
Page 69: ...66 MENU K ALARMS LIMITS Service Level continued Control Only...
Page 82: ...78...
Page 133: ...129 Wiring Connections...