MENU K
– ALARMS & LIMITS (Service Level) continued - Custom Outputs
Alm Output Function 1
#1 #2 #3 #4
C1 Hi Prr Y N N N C1
Low Pr Y N N N C2 Hi
Pr Y N N N C2 Low
Pr Y N N N Short
Cycl Y N N N Maint
Timer Y N N N
C1 Hi Pr:
Circuit #1 high pressure alarm.
C1 Low Pr:
Circuit #1 low pressure alarm.
C2 Hi Pr:
Circuit #2 high pressure alarm.
C2 Low Pr:
Circuit #2 low pressure alarm.
Short Cycl:
One or more compressors has caused a short cycle alarm.
Maint Timer:
Maintenance timer alarm.
Alm Output Function 3
#1 #2 #3 #4
Hi Humid
Y
N
N
N
Low Humid
Y
N
N
N
Humidifier
Y
N
N
N
DA Low T
Y
N
N
N
RA Low T
Y
N
N
N
RA Hi Temp
Y
N
N
N
Hi Humid:
High return air humidity alarm.
Low Humid:
Low return air humidity alarm.
Humidifier:
Humidifier fault alarm.
DA Low T:
Discharge air low temperature alarm.
RA Low T:
Return air low temperature alarm.
RA Hi Temp:
Return air high temperature alarm.