27
018717 • Version
1.1 • 23.01.2007
Mounting,
continued
Procedure,
continued,
continued
Step
Action
6
Seal the unit on the back with the
enclosed gasket to make sure
there are no leaks between the
shelter and the unit. The sealing
must be placed all around at the
outside edge of the unit
7
Lift up the unit and place it very
carefully on the two wall brackets
and press it against the shelter
wall
You must be certain that the
wall of the shelter can bear the
weight of the
Silencio
unit.
Weight of the
Silencio
: > 250 kg
If the wall is not strong enough
you must reinforce the wall!
8
Fasten the unit to the shelter by:
•
Drilling 3 holes through the
bracket and the shelter wall
•
Put one round head square
neck bolt M8 x 130 mm
through the drilled holes from
the inside and out
Note: the enclosed bolts are
suitable for wall thicknesses
up to 100 mm.
For wall thicknesses over 100
mm: Please find suitable bolts
•
Fasten with 3 × Washer M8
and 3 × nut M8 on the outside
Continued overleaf
Gasket