Illustration
This drawing illustrates the different parts
of the cooling circuit and where
they are situated in the AC 24 unit:
Parts and their function
This table gives an overview and short description of each part shown above and on
the next page:
Compressor
Circulates the fluid in the cooling system
Condenser
Emits the heat generated in the tent/room to the outside air
Receiver
Accumulates surplus coolant in connection with the
cooling process
Dry filter
Absorbs moisture and impurities in the cooling circuit
Sight glass
Enables a visual check of the coolant
Expansion valve Supplies the correct quantity of coolant into the evaporator.
It also reduces the pressure
Evaporator
Absorbs heat from the shelter by cooling down the
circulated air
HP pressure
switch
Ensures that the compressor does not operate at too high
pressure
LP Pressure
switch
Ensures that the compressor does not operate at too low
pressure
Refrigerant
The cooling circuit is hermetically sealed and filled with refrigerant (R134a).
Liquid flow
From the receiver
liquid refrigerant will flow under high pressure through the liquid
line dryer and the sight glass to the thermostatic expansion valve which releases the
pressure. Here the refrigerant is led into the evaporator
where it evaporates under
low pressure and low temperatures.
The evaporated refrigerant is drawn back to the hermetic compressor and
compressed. From the compressor the refrigerant vapour goes to the condenser,
where it is cooled to below the dew point and condensed to liquid refrigerant.
Description of the cooling system
14
Summary of Contents for AC-24
Page 1: ...AC 24 SERVICE MANUAL en Rev 1 2 1 2020 W48 3...
Page 2: ......
Page 40: ...40...
Page 47: ...Dimensions Dimensions 47 en...
Page 48: ...Wiring diagram Wiring diagram 48...
Page 49: ...Wiring diagram Continued Wiring diagram continued 49 en...
Page 51: ......