Technical data for the AC 24 units.
*Note: All data regarding heating is only relevant for models with heating coil installed.
Performance
characteristics
The air conditioner has a maximum cooling capacity of 6.0 kW.
When the relative humidity of the air inlet is high, the air can be cooled below its dew point and
thus condense some of the water vapour to free water. This requires a certain amount of latent
cooling but provides a dehumidification process, which is an important factor in comfortable air
supply conditions.
The operating range is between 20 and 55 °C approximately and is controlled by the HP/
LP-pressure switch. In relatively dry locations the air temperature drop will depend on inlet
conditions.
Data
Data and dimensions on the cabinet are shown in the following table:
Specification
Designation
Value 6,0 kW
Dimensions
Height × width × depth
- mm
1110 x 754 x 920 mm
Weight
kg
162
Cabinet material
0.9 mm galvanized sheet
metal plates
Packaging
-
Wooden pallet and
cardboard
Voltage supply
V/PH/Hz
230/1/50
Max current
Amp
16A
Airflow, evaporator,
Standard setup
2
)
m3/h
2,800
Cooling capacity, max
W
6.000
Refrigerant/Load
Type/kg
R134a/2,3
Max. refrigerant pressure
Bar
25
Operation temp. range
C°
20-55
Minimum room
temperature setting
C°
20
GWP
(Global Warming potential)
1430
IP
55
Locked rotor amperange
(LRA)
A
46