background image

DKRCI.PI.FN1.A5.ML / 520H6262 

© Danfoss | DCS (MWA) | 2015.05

ENGLISH

Refrigerants

Applicable to HCFC, HFC, R717 (Ammonia),

R744 (CO

2

) and all flammable refrigerants.

The strainer is only recommended for use 

in closed circuits. For further information 

please contact your local Danfoss sales 

office.
Pressure and temperature range

–60/+150°C (–76/+302°F)

FIA 15-200:

The strainers are designed for a max. 

working pressure of 52 bar (754 psi g)

Installation

Note: 

At delivery the strainer housing is 

not equipped with strainer insert 

or accessories

The strainer must be installed with the top 

cover downwards, and the flow must be 

directed towards the top cover as indicated 

by the arrow on the strainer housing (fig. 

1).  The strainer insert must be inserted 

after welding.

The strainer housing is designed to 

withstand a high internal pressure. 

However, the piping system should be 

designed to avoid liquid traps and reduce 

the risk of hydraulic pressure caused by 

thermal expansion. It must be ensured 

that the strainer is protected from pressure 

transients like “liquid hammer” in the 

system.       

Recommended flow direction

The strainer must be installed with the flow 

towards the top cover as indicated by the 

arrow on the side of the valve body (fig. 

1). Flow in the opposite direction is not 

acceptable. 

Welding

The top cover should be removed before 

welding (fig. 2) to prevent damage to the 

gasket between the strainer housing and 

top cover. Only materials and welding 

methods compatible with the valve 

housing material, must be applied to the 

valve housing. 

 

Clean the strainer housing internally to 

remove welding debris at completion 

of welding and before the strainer is 

reassembled. 

Removing the top cover can be omitted 

provided that:

The temperature in the area between the 

strainer housing and top cover during 

welding does not 150°C/+302°F. 

This temperature depends on the welding 

method as well as on any cooling of the 

strainer housing during the welding itself. 

(Cooling can be ensured by, for example, 

wrapping a wet cloth around the filter 

body). Make sure that no dirt, welding 

debris etc. get into the strainer during the 

welding procedure.

The strainer housing must be free from 

stresses (external loads) after installation.

Strainers must not be mounted in systems 

where the outlet side of the strainer is 

open to atmosphere. The outlet side of the 

strainer must always be connected to the 

system or properly capped off, for example 

with a welded-on end plate.

Assembly

Remove welding debris and any dirt 

from pipes and strainer housing before 

assembly. Check that the strainer insert 

has the right size before it is inserted in 

the top cover and check that the gasket is 

undamaged.

Place the strainer insert (pos. D) from 

underneath. The insert has a slight force fit 

into the housing, no gaskets or O-rings are 

used. 

If magnet inserts have been chosen as 

accessory, fit those on the top cover before 

replacing the cover.

Tightening

Tighten the top cover with a torque 

wrench, to the values indicated in the table 

(fig. 3).

Please note that the table (fig. 3)

containing maximum torque must be

adhered to and never exceeded.

If the drain valve has been chosen as 

accessory, the drain plug should be 

replaced by the drain valve.

Colours and identification

The FIA strainers are painted with a 

red oxide primer in the factory. Precise 

identification of the strainer is made via 

the ID plate on the top cover, as well as by 

the stamping on the strainer housing. The 

external surface of the strainer housing 

must be prevented against corrosion 

with a suitable protective coating after 

installation and assembly.

Be sure to protect the ID plate when 

repainting the strainer.

Maintenance

Mounting of accessory: 

Filter bag (fig. 4)

A 50µ filter bag (pos. E), especially for 

commissioning of the plant, can replace 

the normal strainer insert.

Mount the filter bag (held in place by the 

filter holder) and be sure to place the filter 

bag correctly in the strainer as shown in 

fig. 4.

The flow must go into the filter bag cavity 

and out or else the bag will not function 

properly.

Dismantling the strainer (fig. 3)

Before servicing the strainer, isolate it from 

the system and remove all refrigerant by 

evacuation to zero pressure. Check for 

refrigerant pressure before unscrewing and 

removal of the top cover.

The strainer insert must be removed 

without any use of tools

Cleaning

Clean the strainer insert using an 

appropriate solvent by flushing and 

brushing. The use of strong acids cannot 

be recommended. The strainer insert must 

be wiped or blown dry before inspection. 

If the insert is damaged or the sediments 

cannot be removed, the strainer insert 

must be replaced.

Assembly

Remove any dirt from the housing before 

the strainer is assembled. 

Replacement of gasket

Change the gasket for the top cover (pos. 

C) and drain plug.

Check that the strainer insert is correctly 

placed before remounting the top cover 

and bolts (pos. A).

Tightening (fig. 3)

Tighten the top cover bolts (pos. A) with 

a torque wrench according to the table in 

fig. 3

Use only original Danfoss parts (including  

gaskets) for replacement. Materials of 

new parts are certified for the relevant 

refrigerant. 

In cases of doubt, please contact your local 

Danfoss sales office. 

Summary of Contents for FIA 15-200

Page 1: ...Uwaga W dostarczanym korpusie filtra nie ma wk adu ani akcesori w Observa o Na entrega o corpo do filtro n o est equipado com o elemento filtrante nem com os acess rios Filter bag Flow direction Filte...

Page 2: ...from pipes and strainer housing before assembly Check that the strainer insert has the right size before it is inserted in the top cover and check that the gasket is undamaged Place the strainer inser...

Page 3: ...zu stellen dass es die richtige Gr e hat Auch sicherstellen dass die Dichtung nicht besch digt ist Das Filtersieb Pos D von unten einsetzen Das Filtersieb hat leichte Presspassung im Geh use es werde...

Page 4: ...t de l ins rer dans le couvercle sup rieur et v rifiez que le joint d tanch it n est pas endommag Placez l l ment filtrant pos D par le dessous L l ment s ajuste au corps en for ant l g rement aucun j...

Page 5: ...uebe que la malla de filtro tiene un tama o correcto antes de introducirla en la tapa superior asimismo compruebe que la junta no est da ada Coloque la malla de filtro pos D desde abajo La malla de fi...

Page 6: ...ma di inserirlo nel coperchio superiore e verificare che la guarnizione non sia danneggiata Posizionare l elemento filtrante pos D dal basso L elemento viene montato applicando una leggera pressione s...

Page 7: ...nfoss DCS MWA 2015 05 DKRCI PI FN1 A5 ML 520H6262 7 HCFC HFC R717 R 744 Co 2 Danfoss 60 150 C 76 302 F FIA 15 200 52 bar 754 psi g 1 1 2 150 C 302 F D O 3 3 FIA ID ID 4 50 E 4 3 C A 3 3 A Danfoss Danf...

Page 8: ...wk ad ma prawid owe wymiary a uszczelka jest nieuszkodzona Za o y wk ad filtra poz D od do u Wk ad wchodzi do obudowy na lekki wcisk nie s stosowane adne uszczelki ani pier cienie O ring Je eli jako...

Page 9: ...Danfoss DCS MWA 2015 05 DKRCI PI FN1 A5 ML 520H6262 9 R717 R744 CO2 Danfoss 60 150 C 76 302 F FIA 15 200 52 754 1 1 2 150 C 302 F D 3 3 FIA 4 50 E 4 3 C A 3 A 3 Danfoss...

Page 10: ...antes da montagem Verifique se o elemento filtrante possui o tamanho certo antes de inser lo na tampa superior e verifique se a junta est intacta Coloque o elemento filtrante pos D por debaixo O elem...

Page 11: ...Danfoss DCS MWA 2015 05 DKRCI PI FN1 A5 ML 520H6262 11...

Page 12: ...12 DKRCI PI FN1 A5 ML 520H6262 Danfoss DCS MWA 2015 05...

Reviews: