• Consistent terminal numbers
• Maximum voltage to control card is 24Vdc
• Do NOT connect 120/240/460/575 to Control
terminals
• Use Relay 1 (terminals 01,02, 03) for pilot duty 48 to
240Vac
5) Wiring
f. Control Wiring
5) Wiring the Drive
f. Control Wiring
The maximum voltage for the control circuit must not exceed 24Vdc. Do NOT
connect any voltage higher than 24Vdc for it will cause damage. A separate relay
terminal 01, 02, 03 is used for higher voltages, 48 to 240 Vac.