1.3.4 Fuses

Branch circuit protection
To protect the installation against electrical and fire hazard,
all branch circuits in an installation, switch gear, machines
etc., must be short-circuited and overcurrent protected
according to national/international regulations.

Short circuit protection
Danfoss recommends using the fuses mentioned in the
following tables to protect service personnel or other
equipment in case of an internal failure in the unit or
short-circuit on DC-link. The frequency converter provides
full short circuit protection in case of a short-circuit on the
motor or brake output.

Overcurrent protection
Provide overload protection to avoid overheating of the
cables in the installation. Overcurrent protection must
always be carried out according to national regulations.
Fuses must be designed for protection in a circuit capable
of supplying a maximum of 100,000 A

rms

 (symmetrical),

480 V maximum.

Non UL compliance
If UL/cUL is not to be complied with, Danfoss recommends
using the fuses mentioned in 

Table 1.6

, which ensures

compliance with EN50178/IEC61800-5-1:
In case of malfunction, not following the fuse recommen-
dation may result in damage to the frequency converter
and the installation.

FC 51

Max. Fuses UL

Max. fuses non

UL

Bussmann

Bussmann

Bussmann

Littel fuse

Ferraz-

Shawmut

Ferraz-

Shawmut

1X200-240 V
kW

Type RK1

Type J

Type T

Type RK1

Type CC

Type RK1

Type gG

0K18-0K37

KTN-R15

JKS-15

JJN-15

KLN-R15

ATM-R15

A2K-15R

16A

0K75

KTN-R25

JKS-25

JJN-25

KLN-R25

ATM-R25

A2K-25R

25A

1K5

KTN-R35

JKS-35

JJN-35

KLN-R35

-

A2K-35R

35A

2K2

KTN-R50

JKS-50

JJN-50

KLN-R50

-

A2K-50R

50A

3x200-240 V
0K25

KTN-R10

JKS-10

JJN-10

KLN-R10

ATM-R10

A2K-10R

10A

0K37

KTN-R15

JKS-15

JJN-15

KLN-R15

ATM-R15

A2K-15R

16A

0K75

KTN-R20

JKS-20

JJN-20

KLN-R20

ATM-R20

A2K-20R

20A

1K5

KTN-R25

JKS-25

JJN-25

KLN-R25

ATM-R25

A2K-25R

25A

2K2

KTN-R40

JKS-40

JJN-40

KLN-R40

ATM-R40

A2K-40R

40A

3K7

KTN-R40

JKS-40

JJN-40

KLN-R40

-

A2K-40R

40A

3x380-480 V
0K37-0K75

KTS-R10

JKS-10

JJS-10

KLS-R10

ATM-R10

A6K-10R

10A

1K5

KTS-R15

JKS-15

JJS-15

KLS-R15

ATM-R15

A2K-15R

16A

2K2

KTS-R20

JKS-20

JJS-20

KLS-R20

ATM-R20

A6K-20R

20A

3K0

KTS-R40

JKS-40

JJS-40

KLS-R40

ATM-R40

A6K405R

40A

4K0

KTS-R40

JKS-40

JJS-40

KLS-R40

ATM-R40

A6K-40R

40A

5K5

KTS-R40

JKS-40

JJS-40

KLS-R40

-

A6K-40R

40A

7K5

KTS-R40

JKS-40

JJS-40

KLS-R40

-

A6K-40R

40A

11K0

KTS-R60

JKS-60

JJS-60

KLS-R60

-

A6K-60R

63A

15K0

KTS-R60

JKS-60

JJS-60

KLS-R60

-

A6K-60R

63A

18K5

KTS-R60

JKS-60

JJS-60

KLS-R60

-

A6K-60R

80A

22K0

KTS-R60

JKS-60

JJS-60

KLS-R60

-

A6K-60R

80A

Table 1.6 Fuses

Quick Guide

VLT

®

 Micro Drive Quick Guide

MG02B702 - VLT

®

 is a registered Danfoss trademark

5

1

1

Summary of Contents for VLT Micro Drive FC 51 Series

Page 1: ...MAKING MODERN LIVING POSSIBLE Quick Guide VLT Micro Drive...

Page 2: ...4 1 3 5 Connecting to Mains and Motor 6 1 3 6 Control Terminals 6 1 3 7 Power Circuit Overview 8 1 3 8 Load Sharing Brake 8 1 4 Programming 9 1 4 1 Programming with LCP 9 1 7 Specifications 14 1 8 Ge...

Page 3: ...uency switching at high power This will generate a leakage current in the earth connection A fault current in the frequency converter at the output power terminals might contain a DC component which c...

Page 4: ...ed Start While the frequency converter is connected to mains the motor can be started stopped using digital commands bus commands references or via the LCP Disconnect the frequency converter from main...

Page 5: ...5 140 248 9 5 1 For with potentiometer add 7 6 mm Table 1 4 Mechanical Dimensions 1 3 3 Electrical Installation in General NOTE All cabling must comply with national and local regulations on cable cro...

Page 6: ...ation FC 51 Max Fuses UL Max fuses non UL Bussmann Bussmann Bussmann Littel fuse Ferraz Shawmut Ferraz Shawmut 1X200 240 V kW Type RK1 Type J Type T Type RK1 Type CC Type RK1 Type gG 0K18 0K37 KTN R15...

Page 7: ...hten Illustration 1 2 Mounting of Earth Cable Mains and Motor Wires 1 3 6 Control Terminals All control cable terminals are located underneath the terminal cover in front of the frequency converter Re...

Page 8: ...Illustration 1 5 Overview of Control Terminals in PNP configuration and Factory Setting Quick Guide VLT Micro Drive Quick Guide MG02B702 VLT is a registered Danfoss trademark 7 1 1...

Page 9: ...sharing 1 3 8 Load Sharing Brake Use 6 3 mm insulated Faston Plugs designed for high voltage for DC Load Sharing and brake Contact Danfoss or see instruction MI50N for load sharing and instruction MI...

Page 10: ...ccepting changes to parameter settings Pressing OK for more than 1 s enters Adjust mode In Adjust mode it is possible to make fast adjustment by pressing combined with OK Press to change value Press O...

Page 11: ...0 199 100 1 62 Slip Compensation 400 399 100 1 63 Slip Compensation Time Constant 0 05 5 00 s 0 10 s 1 7 Start Adjustments 1 71 Start Delay 0 0 10 0 s 0 0 s 1 72 Start Function 0 DC hold delay time 1...

Page 12: ...f Delay Relay 0 00 600 00 s 0 01 s 5 5 Pulse Input 5 55 Terminal 33 Low Frequency 20 4999 Hz 20 Hz 5 56 Terminal 33 High Frequency 21 5000 Hz 5000 Hz 5 57 Term 33 Low Ref Feedb Value 4999 4999 0 000 5...

Page 13: ...40 Logic Rule Boolean 1 See par 13 01 0 False 30 32 SL Time out 0 2 13 41 Logic Rule Operator 1 0 Disabled 1 And 2 Or 3 And not 4 Or not 5 Not and 6 Not or 7 Not and not 8 Not or not 13 42 Logic Rule...

Page 14: ...nnected working 29 Power board over temp X X X Heat sink cut out temperature has been reached 30 Motor phase U missing X X Motor phase U is missing Check the phase 31 Motor phase V missing X X Motor p...

Page 15: ...3x200 240 V AC 1 At rated load conditions 1 7 2 Mains Supply 3x200 240 V AC Normal overload 150 for 1 min Typical Shaft Output kW PK25 0 25 PK37 0 37 PK75 0 75 P1K5 1 5 P2K2 2 2 P3K7 3 7 Typical Shaft...

Page 16: ...ns Supply 3x380 480 V AC 1 At rated load conditions Normal overload 150 for 1 minute Frequency converter Typical Shaft Output kW P5K5 5 5 P7K5 7 5 P11K 11 P15K 15 P18K 18 5 P22K 22 Typical Shaft Outpu...

Page 17: ...ering not more than 100 000 RMS symmetrical Amperes 240 480 V maximum Motor output U V W Output voltage 0 100 of supply voltage Output frequency 0 200 Hz VVCplus 0 400 Hz u f Switching on output Unlim...

Page 18: ...lay output Programmable relay output 1 Relay 01 Terminal number 01 03 break 01 02 make Max terminal load AC 1 1 on 01 02 NO Resistive load 250 V AC 2 A Max terminal load AC 15 1 on 01 02 NO Inductive...

Page 19: ...the max ambient temperature If the frequency converter is operated at high ambient temperature the continuous output current should be decreased The frequency converter has been designed for operation...

Page 20: ...e spare parts kits 132B0129 M4 frame spare parts kits 132B0130 M5 frame spare parts kits 132B0131 Blank cover 130B2522 MCC 107 filter for 132F0001 130B2522 MCC 107 filter for 132F0002 130B2533 MCC 107...

Page 21: ...g 2 H Hand Mode 11 I IP21 19 Isolated Mains Source 3 IT Mains 3 L Load Compensation 10 Sharing Brake 8 M Main Menu 9 Mains Supply 14 Supply L1 L L2 L3 N 16 Supply 3x200 240 V AC 14 Supply 3x380 480 V...

Page 22: ...istor 10 U UL Compliance 5 V VLT Control Panel LCP 11 19 Control Panel LCP 12 19 Voltage Level 16 W Warnings And Alarms 13 Index VLT Micro Drive Quick Guide MG02B702 VLT is a registered Danfoss tradem...

Page 23: ...www danfoss com drives MG02B702 132R0029 MG02B702 Rev 2012 03 17...

Reviews: