8-4* FC MC protocol set

8-43 FC Port PCD Read Configuration

*[0] None Expressionlimit

[1] [1500] Operation Hours

[2] [1501] Running Hours

[3] [1502] kWh Counter

[4] [1600] Control Word

[5] [1601] Reference [Unit]

[6] [1602] Reference %

[7] [1603] Status Word

[8] [1605] Main Actual Value [%]

[9] [1609] Custom Readout

[10] [1610] Power [kW]

[11] [1611] Power [hp]

[12] [1612] Motor Voltage

[13] [1613] Frequency

[14] [1614] Motor Current

[15] [1615] Frequency [%]

[16] [1618] Motor Thermal

[17] [1630] DC Link Voltage

[18] [1634] Heatsink Temp.

[19] [1635] Inverter Thermal

[20] [1638] SL Controller State

[21] [1650] External Reference

[22] [1651] Pulse Reference

[23] [1652] Feedback [Unit]

[24] [1660] Digital Input 18,19,27,33

[25] [1661] Digtial Input 29

[26] [1662] Analog Input 53 (V)

[27] [1663] Analog Input 53 (mA)

[28] [1664] Analog Input 60

[29] [1665] Analog Output 42 [mA]

[30] [1668] Freq. Input 33 [Hz]

[31] [1671] Relay Output [bin]

[32] [1672] Counter A

[33] [1673] Counter B

[34] [1690] Alarm Word

[35] [1692] Warning Word

[36] [1694] Ext. Status Word

8-5* Digital/Bus

8-50 Coasting Select

[0] DigitalInput

[1] Bus

[2] LogicAnd

*[3] LogicOr

8-51 Quick Stop Select

See par. 8-50 * [3] LogicOr

8-52 DC Brake Select

See par. 8-50 *[3] LogicOr

8-53 Start Select

See par. 8-50 *[3] LogicOr

8-54 Reversing Select

See par. 8-50 *[3] LogicOr

8-55 Set-up Select

See par. 8-50 *[3] LogicOr

8-56 Preset Reference Select

See par. 8-50 * [3] LogicOr

8-8* Bus communication

Diagnostics

8-80 Bus Message Count

0-0 N/A *0 N/A

8-81 Bus Error Count

0-0 N/A *0 N/A

8-82 Slave Messages Rcvd

0-0 N/A *0 N/A

8-83 Slave Error Count

0-0 N/A *0 N/A

8-9* Bus Jog / Feedback

8-94 Bus feedback 1

0x8000-0x7FFF *0

13-** Smart Logic

13-0* SLC Settings

13-00 SL Controller Mode

*[0] Off

[1] On

13-01 Start Event

[0] False

[1] True

[2] Running

[3] InRange

[4] OnReference

[7] OutOfCurrentRange

[8] BelowILow

[9] AboveIHigh

[16] ThermalWarning

[17] MainOutOfRange

[18] Reversing

[19] Warning

[20] Alarm_Trip

[21] Alarm_TripLock

[22-25] Comparator 0-3

[26-29] LogicRule0-3

[33] DigitalInput_18

[34] DigitalInput_19

[35] DigitalInput_27

[36] DigitalInput_29

[38] DigitalInput_33

*[39] StartCommand

[40] DriveStopped

13-02 Stop Event

See par. 13-01 * [40] DriveStopped

13-03 Reset SLC

*[0] Do not reset

[1] Reset SLC

13-1* Comparators

13-10 Comparator Operand

*[0] Disabled

[1] Reference

[2] Feedback

[3] MotorSpeed

[4] MotorCurrent

[6] MotorPower

[7] MotorVoltage

[8] DCLinkVoltage

[12] AnalogInput53

[13] AnalogInput60

[18] PulseInput33

[20] AlarmNumber

[30] CounterA

[31] CounterB

13-11 Comparator Operator

[0] Less Than

*[1] Approximately equals

[2] Greater Than

13-12 Comparator Value

-9999-9999 *0.0

13-2* Timers

13-20 SL Controller Timer

0.0-3600 s *0.0 s

13-4* Logic Rules

13-40 Logic Rule Boolean 1

See par. 13-01 *[0] False

[30] - [32] SL Time-out 0-2

13-41 Logic Rule Operator 1

*[0] Disabled

[1] And

[2] Or

[3] And not

[4] Or not

[5] Not and

[6] Not or

[7] Not and not

[8] Not or not

13-42 Logic Rule Boolean 2

See par. 13-40 * [0] False

13-43 Logic Rule Operator 2

See par. 13-41 *[0] Disabled

13-44 Logic Rule Boolean 3

See par. 13-40 * [0] False

13-5* States

13-51 SL Controller Event

See par. 13-40 *[0] False

13-52 SL Controller Action

*[0] Disabled

[1] NoAction

[2] SelectSetup1

[3] SelectSetup2

[10-17] SelectPresetRef0-7

[18] SelectRamp1

[19] SelectRamp2

[22] Run

[23] RunReverse

[24] Stop

[25] Qstop

[26] DCstop

[27] Coast

[28] FreezeOutput

[29] StartTimer0

[30] StartTimer1

[31] StartTimer2

[32] Set Digital Output A Low

[33] Set Digital Output B Low

[38] Set Digital Output A High

[39] Set Digital Output B High

[60] ResetCounterA

[61] ResetCounterB

14-** Special Functions

14-0* Inverter Switching

14-01 Switching Frequency

[0] 2 kHz

*[1] 4 kHz

[2] 8 kHz

[4] 16 kHz not available for M5

14-03 Overmodulation

[0] Off

*[1] On

14-1* Mains monitoring

14-12 Function at mains imbalance

*[0] Trip

[1] Warning

[2] Disabled

14-2* Trip Reset

14-20 Reset Mode

*[0] Manual reset

[1-9] AutoReset 1-9

[10] AutoReset 10

[11] AutoReset 15

[12] AutoReset 20

[13] Infinite auto reset

[14] Reset at power up

14-21 Automatic Restart Time

0 - 600s * 10s

14-22 Operation Mode

*[0] Normal Operation

[2] Initialisation

14-26 Action At Inverter Fault

*[0] Trip

[1] Warning

14-4* Energy Optimising

14-41 AEO Minimum Magnetisation

40 - 75 % * 66 %

15-** Drive Information

15-0* Operating Data

15-00 Operating Days

15-01 Running Hours

15-02 kWh Counter

15-03 Power Ups

15-04 Over Temps

15-05 Over Volts

15-06 Reset kWh Counter

*[0] Do not reset

[1] Reset counter

15-07 Reset Running Hours Counter

*[0] Do not reset

[1] Reset counter

15-3* Fault Log

15-30 Fault Log: Error Code

15-4* Drive Identification

15-40 FC Type

15-41 Power Section

15-42 Voltage

15-43 Software Version

15-46 Frequency Converter Order.

No

15-48 Id No

15-51 Frequency Converter Serial

No

16-** Data Readouts 16-0* General

Status

16-00 Control Word

0-0XFFFF

16-01 Reference [Unit]

-4999-4999 *0.000

16-02 Reference %

-200.0-200.0% *0.0%

16-03 Status Word

0-0XFFFF

16-05 Main Actual Value [%]

-200.0-200.0% *0.0%

16-09 Custom Readout

Dep. on par. 0-31, 0-32 and 4-14

16-1* Motor Status

16-10 Power [kW]

16-11 Power [hp]

16-12 Motor Voltage [V]

16-13 Frequency [Hz]

16-14 Motor Current [A]

16-15 Frequency [%]

16-18 Motor Thermal [%]

16-3* Drive Status

16-30 DC Link Voltage

16-34 Heatsink Temp.

16-35 Inverter Thermal

16-36 Inv.Nom. Current

16-37 Inv. Max. Current

16-38 SL Controller State

16-5* Ref./Feedb.

16-50 External Reference

16-51 Pulse Reference

16-52 Feedback [Unit]

Table 1.10

Quick Guide

VLT

®

 Micro Drive Quick Guide

12

MG02B702 - VLT

®

 is a registered Danfoss trademark

1

1

Summary of Contents for VLT Micro Drive FC 51 Series

Page 1: ...MAKING MODERN LIVING POSSIBLE Quick Guide VLT Micro Drive...

Page 2: ...4 1 3 5 Connecting to Mains and Motor 6 1 3 6 Control Terminals 6 1 3 7 Power Circuit Overview 8 1 3 8 Load Sharing Brake 8 1 4 Programming 9 1 4 1 Programming with LCP 9 1 7 Specifications 14 1 8 Ge...

Page 3: ...uency switching at high power This will generate a leakage current in the earth connection A fault current in the frequency converter at the output power terminals might contain a DC component which c...

Page 4: ...ed Start While the frequency converter is connected to mains the motor can be started stopped using digital commands bus commands references or via the LCP Disconnect the frequency converter from main...

Page 5: ...5 140 248 9 5 1 For with potentiometer add 7 6 mm Table 1 4 Mechanical Dimensions 1 3 3 Electrical Installation in General NOTE All cabling must comply with national and local regulations on cable cro...

Page 6: ...ation FC 51 Max Fuses UL Max fuses non UL Bussmann Bussmann Bussmann Littel fuse Ferraz Shawmut Ferraz Shawmut 1X200 240 V kW Type RK1 Type J Type T Type RK1 Type CC Type RK1 Type gG 0K18 0K37 KTN R15...

Page 7: ...hten Illustration 1 2 Mounting of Earth Cable Mains and Motor Wires 1 3 6 Control Terminals All control cable terminals are located underneath the terminal cover in front of the frequency converter Re...

Page 8: ...Illustration 1 5 Overview of Control Terminals in PNP configuration and Factory Setting Quick Guide VLT Micro Drive Quick Guide MG02B702 VLT is a registered Danfoss trademark 7 1 1...

Page 9: ...sharing 1 3 8 Load Sharing Brake Use 6 3 mm insulated Faston Plugs designed for high voltage for DC Load Sharing and brake Contact Danfoss or see instruction MI50N for load sharing and instruction MI...

Page 10: ...ccepting changes to parameter settings Pressing OK for more than 1 s enters Adjust mode In Adjust mode it is possible to make fast adjustment by pressing combined with OK Press to change value Press O...

Page 11: ...0 199 100 1 62 Slip Compensation 400 399 100 1 63 Slip Compensation Time Constant 0 05 5 00 s 0 10 s 1 7 Start Adjustments 1 71 Start Delay 0 0 10 0 s 0 0 s 1 72 Start Function 0 DC hold delay time 1...

Page 12: ...f Delay Relay 0 00 600 00 s 0 01 s 5 5 Pulse Input 5 55 Terminal 33 Low Frequency 20 4999 Hz 20 Hz 5 56 Terminal 33 High Frequency 21 5000 Hz 5000 Hz 5 57 Term 33 Low Ref Feedb Value 4999 4999 0 000 5...

Page 13: ...40 Logic Rule Boolean 1 See par 13 01 0 False 30 32 SL Time out 0 2 13 41 Logic Rule Operator 1 0 Disabled 1 And 2 Or 3 And not 4 Or not 5 Not and 6 Not or 7 Not and not 8 Not or not 13 42 Logic Rule...

Page 14: ...nnected working 29 Power board over temp X X X Heat sink cut out temperature has been reached 30 Motor phase U missing X X Motor phase U is missing Check the phase 31 Motor phase V missing X X Motor p...

Page 15: ...3x200 240 V AC 1 At rated load conditions 1 7 2 Mains Supply 3x200 240 V AC Normal overload 150 for 1 min Typical Shaft Output kW PK25 0 25 PK37 0 37 PK75 0 75 P1K5 1 5 P2K2 2 2 P3K7 3 7 Typical Shaft...

Page 16: ...ns Supply 3x380 480 V AC 1 At rated load conditions Normal overload 150 for 1 minute Frequency converter Typical Shaft Output kW P5K5 5 5 P7K5 7 5 P11K 11 P15K 15 P18K 18 5 P22K 22 Typical Shaft Outpu...

Page 17: ...ering not more than 100 000 RMS symmetrical Amperes 240 480 V maximum Motor output U V W Output voltage 0 100 of supply voltage Output frequency 0 200 Hz VVCplus 0 400 Hz u f Switching on output Unlim...

Page 18: ...lay output Programmable relay output 1 Relay 01 Terminal number 01 03 break 01 02 make Max terminal load AC 1 1 on 01 02 NO Resistive load 250 V AC 2 A Max terminal load AC 15 1 on 01 02 NO Inductive...

Page 19: ...the max ambient temperature If the frequency converter is operated at high ambient temperature the continuous output current should be decreased The frequency converter has been designed for operation...

Page 20: ...e spare parts kits 132B0129 M4 frame spare parts kits 132B0130 M5 frame spare parts kits 132B0131 Blank cover 130B2522 MCC 107 filter for 132F0001 130B2522 MCC 107 filter for 132F0002 130B2533 MCC 107...

Page 21: ...g 2 H Hand Mode 11 I IP21 19 Isolated Mains Source 3 IT Mains 3 L Load Compensation 10 Sharing Brake 8 M Main Menu 9 Mains Supply 14 Supply L1 L L2 L3 N 16 Supply 3x200 240 V AC 14 Supply 3x380 480 V...

Page 22: ...istor 10 U UL Compliance 5 V VLT Control Panel LCP 11 19 Control Panel LCP 12 19 Voltage Level 16 W Warnings And Alarms 13 Index VLT Micro Drive Quick Guide MG02B702 VLT is a registered Danfoss tradem...

Page 23: ...www danfoss com drives MG02B702 132R0029 MG02B702 Rev 2012 03 17...

Reviews: