4-** Limits/Warnings

4-1* Motor Limits

4-10 Motor Speed Direction

*[0] Clockwise If Par. 1-00 is set to

close loop control

[1] CounterClockwise

*[2] Both if Par. 1-00 is set to open

loop control

4-12 Motor Speed Low Limit [Hz]

0.0-400.0 Hz *0.0 Hz

4-14 Motor Speed High Limit [Hz]

0.1-400.0 Hz *65.0 Hz

4-16 Torque Limit Motor Mode

0-400% *150%

4-17 Torque Limit Generator Mode

0-400% *100%

4-4* Adj. Warnings 2

4-40 Warning Frequency Low

0.00 - Value of 4-41 Hz *0.0 Hz

4-41 Warning Frequency High

Value of 4-40-400.0 Hz *400.00 Hz

4-5* Adj. Warnings

4-50 Warning Current Low

0.00-100.00 A *0.00 A

4-51 Warning Current High

0.0-100.00 A *100.00 A

4-54 Warning Reference Low

-4999.000 - Value of 4-55

* -4999.000

4-55 Warning Reference High

Value of 4-54 -4999.000

*4999.000

4-56 Warning Feedback Low

-4999.000 - Value of 4-57

* -4999.000

4-57 Warning Feedback High

Value of 4-56-4999.000 *4999.000

4-58 Missing Motor Phase Function

[0] Off

*[1] On

4-6* Speed Bypass

4-61 Bypass Speed From [Hz]

0.0-400.0 Hz *0.0 Hz

4-63 Bypass Speed To [Hz]

0.0 -400.0 Hz *0.0 Hz

5-1* Digital Inputs

5-10 Terminal 18 Digital Input

[0] No function

[1] Reset

[2] Coast inverse

[3] Coast and reset inv.

[4] Quick stop inverse

[5] DC-brake inv.

[6] Stop inv

*[8] Start

[9] Latched start

[10] Reversing

[11] Start reversing

[12] Enable start forward

[13] Enable start reverse

[14] Jog

[16-18] Preset ref bit 0-2

[19] Freeze reference

[20] Freeze output

[21] Speed up

[22] Speed down

[23] Setup select bit 0

[28] Catch up

[29] Slow down

[34] Ramp bit 0

[60] Counter A (up)

[61] Counter A (down)

[62] Reset counter A

[63] Counter B (up)

[64] Counter B (down)

[65] ResetCounter B

5-11 Terminal 19 Digital Input

See par. 5-10. * [10] Reversing

5-12 Terminal 27 Digital Input

See par. 5-10. * [1] Reset

5-13 Terminal 29 Digital Input

See par. 5-10. * [14] Jog

5-15 Terminal 33 Digital Input

See par. 5-10. * [16] Preset ref bit 0

[26] Precise Stop Inverse

[27] Start, Precise Stop

[32] Pulse Input

5-3* Digital Outputs

5-34 On Delay, Terminal 42 Digital

Output

0.00 - 600.00 s * 0.01 s

5-35 Off Delay, Terminal 42 Digital

Output

0.00 - 600.00 s * 0.01 s

5-4* Relays

5-40 Function Relay

*[0] No operation

[1] Control ready

[2] Drive ready

[3] Drive ready, Remote

[4] Enable / No warning

[5] Drive running

[6] Running / No warning

[7] Run in range / No warning

[8] Run on ref / No warning

[9] Alarm

[10] Alarm or warning

[12] Out of current range

[13] Below current, low

[14] Above current, high

[16] Below frequency, low

[17] Above frequency, high

[19] Below feedback, low

[20] Above feedback, high

[21] Thermal warning

[22] Ready, No thermal warning

[23] Remote ready, No thermal

warning

[24] Ready, Voltage ok

[25] Reverse

[26] Bus ok

[28] Brake,NoWarn

[29] Brake ready/NoFault

[30] BrakeFault (IGBT)

[32] Mech.brake control

[36] Control word bit 11

[41] Below reference, low

[42] Above reference, high

[51] Local ref. active

[52] Remote ref. active

[53] No alarm

[54] Start cmd active

[55] Running reverse

[56] Drive in hand mode

[57] Drive in auto mode

[60-63] Comparator 0-3

[70-73] Logic rule 0-3

[81] SL digital output B

5-41 On Delay, Relay

0.00-600.00 s *0.01 s

5-42 Off Delay, Relay

0.00-600.00 s *0.01 s

5-5* Pulse Input

5-55 Terminal 33 Low Frequency

20-4999 Hz *20 Hz

5-56 Terminal 33 High Frequency

21-5000 Hz *5000 Hz

5-57 Term. 33 Low Ref./Feedb.

Value

-4999-4999 *0.000

5-58 Term. 33 High Ref./Feedb.

Value

-4999-4999 *50.000

6-** Analog In/Out

6-0* Analog I/O Mode

6-00 Live Zero Timeout Time

1-99 s *10 s

6-01 Live Zero TimeoutFunction

*[0] Off

[1] Freeze output

[2] Stop

[3] Jogging

[4] Max speed

[5] Stop and trip

6-1* Analog Input 1

6-10 Terminal 53 Low Voltage

0.00-9.99 V *0.07 V

6-11 Terminal 53 High Voltage

0.01-10.00 V *10.00 V

6-12 Terminal 53 Low Current

0.00-19.99 mA *0.14 mA

6-13 Terminal 53 High Current

0.01-20.00 mA *20.00 mA

6-14 Term. 53 Low Ref./Feedb.

Value

-4999-4999 *0.000

6-15 Term. 53 High Ref./Feedb.

Value

-4999-4999 *50.000

6-16 Terminal 53 Filter Time

Constant

0.01-10.00 s *0.01 s

6-19 Terminal 53 mode

*[0] Voltage mode

[1] Current mode

6-2* Analog Input 2

6-22 Terminal 60 Low Current

0.00-19.99 mA *0.14 mA

6-23 Terminal 60 High Current

0.01-20.00 mA *20.00 mA

6-24 Term. 60 Low Ref./Feedb.

Value

-4999-4999 *0.000

6-25 Term. 60 High Ref./Feedb.

Value

-4999-4999 *50.00

6-26 Terminal 60 Filter Time

Constant

0.01-10.00 s *0.01 s

6-8* potentiometer

6-80 LCP Potmeter Enable

[0] Disabled

*[1] Enable

6-81 potm. Low Reference

-4999-4999 *0.000

6-82 potm. High Reference

-4999-4999 *50.00

6-9* Analog Output xx

6-90 Terminal 42 Mode

*[0] 0-20 mA

[1] 4-20 mA

[2] Digital Output

6-91 Terminal 42 Analog Output

*[0] No operation

[10] Output Frequency

[11] Reference

[12] Feedback

[13] Motor Current

[16] Power

[20] Bus Reference

6-92 Terminal 42 Digital Output

See par. 5-40

*[0] No Operation

[80] SL Digital Output A

6-93 Terminal 42 Output Min Scale

0.00-200.0% *0.00%

6-94 Terminal 42 Output Max Scale

0.00-200.0% *100.0%

7-** Controllers

7-2* Process Ctrl. Feedb

7-20 Process CL Feedback 1

Resource

*[0] NoFunction

[1] Analog Input 53

[2] Analog input 60

[8] PulseInput33

[11] LocalBusRef

7-3* Process PI

Ctrl. 7-30 Process PI Normal/

Inverse Ctrl

*[0] Normal

[1] Inverse

7-31 Process PI Anti Windup

[0] Disable

*[1] Enable

7-32 Process PI Start Speed

0.0-200.0 Hz *0.0 Hz

7-33 Process PI Proportional Gain

0.00-10.00 *0.01

7-34 Process PI Integral Time

0.10-9999 s *9999 s

7-38 Process PI Feed Forward

Factor

0-400% *0%

7-39 On Reference Bandwidth

0-200% *5%

8-** Comm. and Options

8-0* General Settings

8-01 Control Site

*[0] Digital and ControlWord

[1] Digital only

[2] ControlWord only

8-02 Control Word Source

[0] None

*[1] FC RS485

8-03 Control Word Timeout Time

0.1-6500 s *1.0 s

8-04 Control Word Timeout

Function

*[0] Off

[1] Freeze Output

[2] Stop

[3] Jogging

[4] Max. Speed

[5] Stop and trip

8-06 Reset Control Word Timeout

*[0] No Function

[1] Do reset

8-3* FC Port Settings

8-30 Protocol

*[0] FC

[2] Modbus

8-31 Address

1-247 *1

8-32 FC Port Baud Rate

[0] 2400 Baud

[1] 4800 Baud

*[2] 9600 Baud For choose FC Bus

in 8-30

*[3] 19200 Baud For choose

Modbus in 8-30

[4] 38400 Baud

8-33 FC Port Parity

*[0] Even Parity, 1 Stop Bit

[1] Odd Parity, 1 Stop Bit

[2] No Parity, 1 Stop Bit

[3] No Parity, 2 Stop Bits

8-35 Minimum Response Delay

0.001-0.5 *0.010 s

8-36 Max Response Delay

0.100-10.00 s *5.000 s

Table 1.9

Quick Guide

VLT

®

 Micro Drive Quick Guide

MG02B702 - VLT

®

 is a registered Danfoss trademark

11

1

1

Summary of Contents for VLT Micro Drive FC 51 Series

Page 1: ...MAKING MODERN LIVING POSSIBLE Quick Guide VLT Micro Drive...

Page 2: ...4 1 3 5 Connecting to Mains and Motor 6 1 3 6 Control Terminals 6 1 3 7 Power Circuit Overview 8 1 3 8 Load Sharing Brake 8 1 4 Programming 9 1 4 1 Programming with LCP 9 1 7 Specifications 14 1 8 Ge...

Page 3: ...uency switching at high power This will generate a leakage current in the earth connection A fault current in the frequency converter at the output power terminals might contain a DC component which c...

Page 4: ...ed Start While the frequency converter is connected to mains the motor can be started stopped using digital commands bus commands references or via the LCP Disconnect the frequency converter from main...

Page 5: ...5 140 248 9 5 1 For with potentiometer add 7 6 mm Table 1 4 Mechanical Dimensions 1 3 3 Electrical Installation in General NOTE All cabling must comply with national and local regulations on cable cro...

Page 6: ...ation FC 51 Max Fuses UL Max fuses non UL Bussmann Bussmann Bussmann Littel fuse Ferraz Shawmut Ferraz Shawmut 1X200 240 V kW Type RK1 Type J Type T Type RK1 Type CC Type RK1 Type gG 0K18 0K37 KTN R15...

Page 7: ...hten Illustration 1 2 Mounting of Earth Cable Mains and Motor Wires 1 3 6 Control Terminals All control cable terminals are located underneath the terminal cover in front of the frequency converter Re...

Page 8: ...Illustration 1 5 Overview of Control Terminals in PNP configuration and Factory Setting Quick Guide VLT Micro Drive Quick Guide MG02B702 VLT is a registered Danfoss trademark 7 1 1...

Page 9: ...sharing 1 3 8 Load Sharing Brake Use 6 3 mm insulated Faston Plugs designed for high voltage for DC Load Sharing and brake Contact Danfoss or see instruction MI50N for load sharing and instruction MI...

Page 10: ...ccepting changes to parameter settings Pressing OK for more than 1 s enters Adjust mode In Adjust mode it is possible to make fast adjustment by pressing combined with OK Press to change value Press O...

Page 11: ...0 199 100 1 62 Slip Compensation 400 399 100 1 63 Slip Compensation Time Constant 0 05 5 00 s 0 10 s 1 7 Start Adjustments 1 71 Start Delay 0 0 10 0 s 0 0 s 1 72 Start Function 0 DC hold delay time 1...

Page 12: ...f Delay Relay 0 00 600 00 s 0 01 s 5 5 Pulse Input 5 55 Terminal 33 Low Frequency 20 4999 Hz 20 Hz 5 56 Terminal 33 High Frequency 21 5000 Hz 5000 Hz 5 57 Term 33 Low Ref Feedb Value 4999 4999 0 000 5...

Page 13: ...40 Logic Rule Boolean 1 See par 13 01 0 False 30 32 SL Time out 0 2 13 41 Logic Rule Operator 1 0 Disabled 1 And 2 Or 3 And not 4 Or not 5 Not and 6 Not or 7 Not and not 8 Not or not 13 42 Logic Rule...

Page 14: ...nnected working 29 Power board over temp X X X Heat sink cut out temperature has been reached 30 Motor phase U missing X X Motor phase U is missing Check the phase 31 Motor phase V missing X X Motor p...

Page 15: ...3x200 240 V AC 1 At rated load conditions 1 7 2 Mains Supply 3x200 240 V AC Normal overload 150 for 1 min Typical Shaft Output kW PK25 0 25 PK37 0 37 PK75 0 75 P1K5 1 5 P2K2 2 2 P3K7 3 7 Typical Shaft...

Page 16: ...ns Supply 3x380 480 V AC 1 At rated load conditions Normal overload 150 for 1 minute Frequency converter Typical Shaft Output kW P5K5 5 5 P7K5 7 5 P11K 11 P15K 15 P18K 18 5 P22K 22 Typical Shaft Outpu...

Page 17: ...ering not more than 100 000 RMS symmetrical Amperes 240 480 V maximum Motor output U V W Output voltage 0 100 of supply voltage Output frequency 0 200 Hz VVCplus 0 400 Hz u f Switching on output Unlim...

Page 18: ...lay output Programmable relay output 1 Relay 01 Terminal number 01 03 break 01 02 make Max terminal load AC 1 1 on 01 02 NO Resistive load 250 V AC 2 A Max terminal load AC 15 1 on 01 02 NO Inductive...

Page 19: ...the max ambient temperature If the frequency converter is operated at high ambient temperature the continuous output current should be decreased The frequency converter has been designed for operation...

Page 20: ...e spare parts kits 132B0129 M4 frame spare parts kits 132B0130 M5 frame spare parts kits 132B0131 Blank cover 130B2522 MCC 107 filter for 132F0001 130B2522 MCC 107 filter for 132F0002 130B2533 MCC 107...

Page 21: ...g 2 H Hand Mode 11 I IP21 19 Isolated Mains Source 3 IT Mains 3 L Load Compensation 10 Sharing Brake 8 M Main Menu 9 Mains Supply 14 Supply L1 L L2 L3 N 16 Supply 3x200 240 V AC 14 Supply 3x380 480 V...

Page 22: ...istor 10 U UL Compliance 5 V VLT Control Panel LCP 11 19 Control Panel LCP 12 19 Voltage Level 16 W Warnings And Alarms 13 Index VLT Micro Drive Quick Guide MG02B702 VLT is a registered Danfoss tradem...

Page 23: ...www danfoss com drives MG02B702 132R0029 MG02B702 Rev 2012 03 17...

Reviews: