background image

16-6* Inputs/Outputs

16-60 Digital Input 18,19,27,33

0-1111

16-61 Digital Input 29

0-1

16-62 Analog Input 53 (volt)

16-63 Analog Input 53 (current)

16-64 Analog Input 60

16-65 Analog Output 42 [mA]

16-68 Pulse Input [Hz]

16-71 Relay Output [bin]

16-72 Counter A

16-73 Counter B

16-8* Fieldbus/FC Port

16-86 FC Port REF 1

0x8000-0x7FFFF

16-9* Diagnosis Readouts

16-90 Alarm Word

0-0XFFFFFFFF

16-92 Warning Word

0-0XFFFFFFFF

16-94 Ext. Status Word

0-0XFFFFFFFF

18-** Extended Motor Data

18-8* Motor Resistors

18-80 Stator Resistance (High

resolution)

0.000-99.990 ohm *0.000 ohm

18-81 Stator Leakage

Reactance(High resolution)

0.000-99.990 ohm *0.000 ohm

Table 1.11

1.6  Troubleshooting

No. Description

Warning Alarm

Trip

Lock

Error

Cause of Problem

2

Live zero error

X

X

 

 

Signal on terminal 53 or 60 is less than 50% of value set in

6-10 Terminal 53 Low Voltage

6-12 Terminal 53 Low Current

and

6-22 Terminal 54 Low Current

.

4

Mains phase loss

1)

X

X

X

 

Missing phase on supply side, or too high voltage imbalance. Check

supply voltage.

7

DC over voltage

1)

X

X

 

 

Intermediate circuit voltage exceeds limit.

8

DC under voltage

1)

X

X

 

 

Intermediate circuit voltage drops below “voltage warning low” limit.

9

Inverter overloaded

X

X

 

 

More than 100% load for too long.

10

Motor ETR over temperature

X

X

 

 

Motor is too hot due to more than 100% load for too long.

11

Motor thermistor over

temperature

X

X

 

 

Thermistor or thermistor connection is disconnected.

12

Torque limit

X

 

 

 

Torque exceeds value set in either par. 4-16 or 4-17.

13

Over Current

X

X

X

 

Inverter peak current limit is exceeded.

14

Earth fault

X

X

X

 

Discharge from output phases to ground.

16

Short Circuit

 

X

X

 

Short-circuit in motor or on motor terminals.

17

Control word timeout

X

X

 

 

No communication to frequency converter.

25

Brake resistor short-circuited

 

X

X

 

Brake resistor is short-circuited, thus brake function is disconnected.

27

Brake chopper short-circuited

 

X

X

 

Brake transistor is short-circuited, thus brake function is discon-

nected.

28

Brake check

 

X

 

 

Brake resistor is not connected/working

29

Power board over temp

X

X

X

 

Heat-sink cut-out temperature has been reached.

30

Motor phase U missing

 

X

X

 

Motor phase U is missing. Check the phase.

31

Motor phase V missing

 

X

X

 

Motor phase V is missing. Check the phase.

32

Motor phase W missing

 

X

X

 

Motor phase W is missing. Check the phase.

38

Internal fault

 

X

X

 

Contact local Danfoss supplier.

44

Earth fault

 

X

X

 

Discharge from output phases to ground.

47

Control Voltage Fault

 

X

X

 

24 V DC may be overloaded.

51

AMT check U

nom

 and I

nom

 

X

 

 

Wrong setting for motor voltage and/or motor current.

52

AMT low I

nom

 

X

 

 

Motor current is too low. Check settings.

59

Current limit

X

 

 

 

VLT overload.

63

Mechanical Brake Low

 

X

 

 

Actual motor current has not exceeded “release brake” current

within “start delay” time window.

80

Drive Initialised to Default Value

 

X

 

 

All parameter settings are initialized to default settings.

84

The connection between drive

and is lost

 

 

 

X

No communication between and frequency converter

85

Button disabled

 

 

 

X

See parameter group 0-4* 

LCP

86

Copy fail

 

 

 

X

An error occurred while copying from frequency converter to LCP or

vice versa.

87

data invalid

 

 

 

X

Occurs when copying from LCP if the LCP contains erroneous data -

or if no data was uploaded to the LCP.

88

data not compatible

 

 

 

X

Occurs when copying from LCP if data are moved between

frequency converters with major differences in software versions.

89

Parameter read only

 

 

 

X

Occurs when trying to write to a read-only parameter.

90

Parameter database busy

 

 

 

X

LCP and RS485 connection are trying to update parameters simulta-

neously.

91

Parameter value is not valid in this

mode

 

 

 

X

Occurs when trying to write an illegal value to a parameter.

92

Parameter value exceeds the

min/max limits

 

 

 

X

Occurs when trying to set a value outside the range.

nw

run

Not While RUNning

 

 

 

X

Parameter can only be changed when the motor is stopped.

Err. A wrong password was entered

 

 

 

X

Occurs when using a wrong password for changing a password-

protected parameter.

1)

 These faults may be caused by mains distortions. Installing Danfoss Line Filter may rectify this problem.

Table 1.12 Warnings and Alarms Code list

Quick Guide

VLT

®

 Micro Drive Quick Guide

MG02B702 - VLT

®

 is a registered Danfoss trademark

13

1

1

Summary of Contents for VLT Micro Drive FC 51 Series

Page 1: ...MAKING MODERN LIVING POSSIBLE Quick Guide VLT Micro Drive...

Page 2: ...4 1 3 5 Connecting to Mains and Motor 6 1 3 6 Control Terminals 6 1 3 7 Power Circuit Overview 8 1 3 8 Load Sharing Brake 8 1 4 Programming 9 1 4 1 Programming with LCP 9 1 7 Specifications 14 1 8 Ge...

Page 3: ...uency switching at high power This will generate a leakage current in the earth connection A fault current in the frequency converter at the output power terminals might contain a DC component which c...

Page 4: ...ed Start While the frequency converter is connected to mains the motor can be started stopped using digital commands bus commands references or via the LCP Disconnect the frequency converter from main...

Page 5: ...5 140 248 9 5 1 For with potentiometer add 7 6 mm Table 1 4 Mechanical Dimensions 1 3 3 Electrical Installation in General NOTE All cabling must comply with national and local regulations on cable cro...

Page 6: ...ation FC 51 Max Fuses UL Max fuses non UL Bussmann Bussmann Bussmann Littel fuse Ferraz Shawmut Ferraz Shawmut 1X200 240 V kW Type RK1 Type J Type T Type RK1 Type CC Type RK1 Type gG 0K18 0K37 KTN R15...

Page 7: ...hten Illustration 1 2 Mounting of Earth Cable Mains and Motor Wires 1 3 6 Control Terminals All control cable terminals are located underneath the terminal cover in front of the frequency converter Re...

Page 8: ...Illustration 1 5 Overview of Control Terminals in PNP configuration and Factory Setting Quick Guide VLT Micro Drive Quick Guide MG02B702 VLT is a registered Danfoss trademark 7 1 1...

Page 9: ...sharing 1 3 8 Load Sharing Brake Use 6 3 mm insulated Faston Plugs designed for high voltage for DC Load Sharing and brake Contact Danfoss or see instruction MI50N for load sharing and instruction MI...

Page 10: ...ccepting changes to parameter settings Pressing OK for more than 1 s enters Adjust mode In Adjust mode it is possible to make fast adjustment by pressing combined with OK Press to change value Press O...

Page 11: ...0 199 100 1 62 Slip Compensation 400 399 100 1 63 Slip Compensation Time Constant 0 05 5 00 s 0 10 s 1 7 Start Adjustments 1 71 Start Delay 0 0 10 0 s 0 0 s 1 72 Start Function 0 DC hold delay time 1...

Page 12: ...f Delay Relay 0 00 600 00 s 0 01 s 5 5 Pulse Input 5 55 Terminal 33 Low Frequency 20 4999 Hz 20 Hz 5 56 Terminal 33 High Frequency 21 5000 Hz 5000 Hz 5 57 Term 33 Low Ref Feedb Value 4999 4999 0 000 5...

Page 13: ...40 Logic Rule Boolean 1 See par 13 01 0 False 30 32 SL Time out 0 2 13 41 Logic Rule Operator 1 0 Disabled 1 And 2 Or 3 And not 4 Or not 5 Not and 6 Not or 7 Not and not 8 Not or not 13 42 Logic Rule...

Page 14: ...nnected working 29 Power board over temp X X X Heat sink cut out temperature has been reached 30 Motor phase U missing X X Motor phase U is missing Check the phase 31 Motor phase V missing X X Motor p...

Page 15: ...3x200 240 V AC 1 At rated load conditions 1 7 2 Mains Supply 3x200 240 V AC Normal overload 150 for 1 min Typical Shaft Output kW PK25 0 25 PK37 0 37 PK75 0 75 P1K5 1 5 P2K2 2 2 P3K7 3 7 Typical Shaft...

Page 16: ...ns Supply 3x380 480 V AC 1 At rated load conditions Normal overload 150 for 1 minute Frequency converter Typical Shaft Output kW P5K5 5 5 P7K5 7 5 P11K 11 P15K 15 P18K 18 5 P22K 22 Typical Shaft Outpu...

Page 17: ...ering not more than 100 000 RMS symmetrical Amperes 240 480 V maximum Motor output U V W Output voltage 0 100 of supply voltage Output frequency 0 200 Hz VVCplus 0 400 Hz u f Switching on output Unlim...

Page 18: ...lay output Programmable relay output 1 Relay 01 Terminal number 01 03 break 01 02 make Max terminal load AC 1 1 on 01 02 NO Resistive load 250 V AC 2 A Max terminal load AC 15 1 on 01 02 NO Inductive...

Page 19: ...the max ambient temperature If the frequency converter is operated at high ambient temperature the continuous output current should be decreased The frequency converter has been designed for operation...

Page 20: ...e spare parts kits 132B0129 M4 frame spare parts kits 132B0130 M5 frame spare parts kits 132B0131 Blank cover 130B2522 MCC 107 filter for 132F0001 130B2522 MCC 107 filter for 132F0002 130B2533 MCC 107...

Page 21: ...g 2 H Hand Mode 11 I IP21 19 Isolated Mains Source 3 IT Mains 3 L Load Compensation 10 Sharing Brake 8 M Main Menu 9 Mains Supply 14 Supply L1 L L2 L3 N 16 Supply 3x200 240 V AC 14 Supply 3x380 480 V...