[1669]
Pulse Output #27 [Hz]
Actual value of pulses applied to terminal 27 in digital output mode.
[1670]
Pulse Output #29 [Hz]
Actual value of pulses applied to terminal 29 in digital output mode.
[1671]
Relay Output [bin]
View the setting of all relays.
[1672]
Counter A
View the present value of Counter A.
[1673]
Counter B
View the present value of Counter B.
[1675]
Analog In X30/11
Actual value of the signal on input X30/11 (General Purpose I/O Card. Option)
[1676]
Analog In X30/12
Actual value of the signal on input X30/12 (General Purpose I/O Card. Optional)
[1677]
Analog Out X30/8 [mA]
Actual value at output X30/8 (General Purpose I/O Card. Optional) Use Par. 6-60 to select the var-
iable to be shown.
[1680]
Fieldbus CTW 1
Control word (CTW) received from the bus master.
[1682]
Fieldbus REF 1
Main reference value sent with control word via the serial communications network, e.g., from the
BMS, PLC or other master controller.
[1684]
Comm. Option Status
Extended serial communication option status word.
[1685]
FC Port CTW 1
Control word (CTW) received from the bus master.
[1686]
FC Port REF 1
Status word (STW) sent to the bus master.
[1690]
Alarm Word
One or more alarms in a Hex code (used for serial communications)
[1691]
Alarm word 2
One or more alarms in a Hex code (used for serial communications)
[1692]
Warning Word
One or more warnings in a Hex code (used for serial communications)
[1693]
Warning word 2
One or more warnings in a Hex code (used for serial communications)
[1694]
Ext. Status Word
One or more status conditions in a Hex code (used for serial communications)
[1695]
Ext. Status Word 2
One or more status conditions in a Hex code (used for serial communications)
[1696]
Maintenance Word
The bits reflect the status for the programmed preventive maintenance events in parameter group
23-1*
[1830]
Analog Input X42/1
Shows the value of the signal applied to terminal X42/1 on the Analog I/O card.
[1831]
Analog Input X42/3
Shows the value of the signal applied to terminal X42/3 on the Analog I/O card.
[1832]
Analog Input X42/5
Shows the value of the signal applied to terminal X42/5 on the Analog I/O card.
[1833]
Analog Out X42/7 [V]
Shows the value of the signal applied to terminal X42/7 on the Analog I/O card.
[1834]
Analog Out X42/9 [V]
Shows the value of the signal applied to terminal X42/9 on the Analog I/O card.
[1835]
Analog Out X42/11 [V]
Shows the value of the signal applied to terminal X42/11 on the Analog I/O card.
[1850]
Sensorless Readout [unit]
[2117]
Ext. 1 Reference [Unit]
The value of the reference for extended Closed-loop Controller 1
[2118]
Ext. 1 Feedback [Unit]
The value of the feedback signal for extended Closed-loop Controller 1
[2119]
Ext. 1 Output [%]
The value of the output from extended Closed-loop Controller 1
[2137]
Ext. 2 Reference [Unit]
The value of the reference for extended Closed-loop Controller 2
[2138]
Ext. 2 Feedback [Unit]
The value of the feedback signal for extended Closed-loop Controller 2
[2139]
Ext. 2 Output [%]
The value of the output from extended Closed-loop Controller 2