22-75 Short Cycle Protection
Option:
Function:
[0] *
Disabled
Timer set in par. 22-76
is disabled.
[1]
Enabled
is enabled.
22-76 Interval between Starts
Range:
Function:
Application
dependent*
[Application dependant]
22-77 Minimum Run Time
Range:
Function:
0 s*
[Application dependant]
Sets the time desired as minimum run time after a normal start command (Start/Jog/Freeze). Any
normal stop command will be disregarded until the set time has expired. The timer will start counting
following a normal start command (Start/Jog/Freeze).
The timer will be overridden by a Coast (Inverse) or an External Interlock command.
NOTE!
Does not work in cascade mode.
22-80 Flow Compensation
Option:
Function:
[0] *
Disabled
[0]
Disabled
: Setpoint compensation not active.
[1]
Enabled
[1]
Enabled
: Setpoint compensation is active. Enabling this parameter allows the Flow Compensated
Setpoint operation.
22-81 Square-linear Curve Approximation
Range:
Function:
100 %*
[0 - 100 %]
Example 1:
Adjustment of this parameter allows the shape of the control curve to be adjusted.
0 = Linear
100% = Ideal shape (theoretical).
NOTE!
Please note: Not visible when running in cascade.