![Danfoss VLT HVACDrive Instruction Manual Download Page 30](http://html1.mh-extra.com/html/danfoss/vlt-hvacdrive/vlt-hvacdrive_instruction-manual_3860104030.webp)
If UL/cUL is not to be complied with, we recommend using the following fuses, which will ensure compliance with EN50178:
Adjustable Frequency Drive
Voltage
Type
P110 - P250
380–480 V
type gG
P315 - P450
380–480 V
type gR
Table 4.4: Compliance with EN50178
UL compliance fuses
Adjustable
frequency
drive
Bussmann
Bussmann
Bussmann
SIBA
Littel fuse
Ferraz-
Shawmut
Ferraz-
Shawmut
200–240 V
kW
Type RK1
Type J
Type T
Type RK1
Type RK1
Type CC
Type RK1
K25-K37
KTN-R05
JKS-05
JJN-05
5017906-005
KLN-R005
ATM-R05
A2K-05R
K55-1K1
KTN-R10
JKS-10
JJN-10
5017906-010
KLN-R10
ATM-R10
A2K-10R
1K5
KTN-R15
JKS-15
JJN-15
5017906-015
KLN-R15
ATM-R15
A2K-15R
2K2
KTN-R20
JKS-20
JJN-20
5012406-020
KLN-R20
ATM-R20
A2K-20R
3K0
KTN-R25
JKS-25
JJN-25
5012406-025
KLN-R25
ATM-R25
A2K-25R
3K7
KTN-R30
JKS-30
JJN-30
5012406-030
KLN-R30
ATM-R30
A2K-30R
5K5
KTN-R50
JKS-50
JJN-50
5012406-050
KLN-R50
-
A2K-50R
7K5
KTN-R50
JKS-60
JJN-60
5012406-050
KLN-R60
-
A2K-50R
11K
KTN-R60
JKS-60
JJN-60
5014006-063
KLN-R60
A2K-60R
A2K-60R
15K
KTN-R80
JKS-80
JJN-80
5014006-080
KLN-R80
A2K-80R
A2K-80R
18K5
KTN-R125
JKS-150
JJN-125
2028220-125
KLN-R125
A2K-125R
A2K-125R
22K
KTN-R125
JKS-150
JJN-125
2028220-125
KLN-R125
A2K-125R
A2K-125R
30K
FWX-150
-
-
2028220-150
L25S-150
A25X-150
A25X-150
37K
FWX-200
-
-
2028220-200
L25S-200
A25X-200
A25X-200
45K
FWX-250
-
-
2028220-250
L25S-250
A25X-250
A25X-250
Table 4.5:
UL fuses, 200–240 V
4 Electrical Installation
VLT
®
HVAC Drive Instruction Manual
4-6
MG.11.AB.22 - VLT
®
is a registered Danfoss trademark
4