NOTE!
If the drive is equipped with a constant speed bypass with an automatic bypass function that starts the bypass if the drive experiences
a persistent alarm condition, be sure to disable the bypass’ automatic bypass function, if [2] Alarm or [3] Man. Reset Alarm is selected
as the dry pump function.
22-27 Dry Pump Delay
Range:
Function:
10 s*
[0 - 600 s]
Defines for how long the Dry Pump condition must be active before activating Warning or Alarm
22-40 Minimum Run Time
Range:
Function:
10 s*
[0 - 600 s]
Set the desired minimum running time for the motor after a start command (digital input or bus)
before entering sleep mode.
22-41 Minimum Sleep Time
Range:
Function:
10 s*
[0 - 600 s]
Set the desired minimum time for staying in sleep mode. This will override any wake-up conditions.
22-42 Wake-up Speed [RPM]
Range:
Function:
Application
dependent*
[Application dependant]
22-43 Wake-up Speed [Hz]
Range:
Function:
Application
dependent*
[Application dependant]
22-44 Wake-up Ref./FB Difference
Range:
Function:
10 %*
[0 - 100 %]
Only to be used if par. 1-00
is set for closed-loop and the integrated PI controller
is used for controlling the pressure.
Set the pressure drop allowed in percentage of setpoint for the pressure (Pset) before canceling the
sleep mode.
NOTE!
If used in application where the integrated PI controller is set for inverse control (e.g., cooling tower applications) in par. 20-71
, the value set in par. 22-44
will automatically be added.