3.1.2. Binary Inputs (BI)
NPT
NPA
UNIT
DESCRIPTION
RANGE
PARAMETER
NUMBER
BI
0
-
Timers Status
0=OK
, 1=Limit
16-84
BI
1
-
Current Status
0=OK
, 1=Limit
16-84
BI
2
-
Voltage Status
0=OK
, 1=Limit
16-84
BI
3
-
Inverter Status
0=OK
, 1 =Stall,
Auto-start
16-84
BI
4
-
Running Status
0=Not Run-
ning , 1
=Running 16-84
BI
5
-
Frequency Status
0=Out of
Range , 1
=In
Range
16-84
BI
6
-
Control Status
0=Local , 1
= Bus 16-84
BI
7
-
Reference Status
0=Not on Ref.,
1
=On Ref.
16-84
BI
8
-
Warning Status
0=No Warning
,
1= Warning
16-84
BI
9
-
Tripped Status
0=No Trip
,
1=Tripped
16-84
BI
10
-
Drive Enabled Sta-
tus
0=Not Enabled
,
1=Enabled
16-84
BI
11
-
Drive Ready Status
0=Not Ready
,
1=Ready
16-84
BI
12
-
Drive Controller
Status
0=Not Ready
,
1=Ready
16-84
BI
16
-
AMA-ze suspicious
UNOM
0=OK
, 1=Warn-
ing
16-92
BI
17
-
AMA-ze suspicious
INOM
0=OK
, 1=Warn-
ing
16-92
BI
18
-
AMA-ze motor too
big
0=OK
, 1=Warn-
ing
16-92
BI
19
-
AMA-ze motor too
small
0=OK
, 1=Warn-
ing
16-92
BI
20
-
Frequency low
0=OK
, 1=Warn-
ing
16-92
BI
21
-
Frequency high
0=OK
, 1=Warn-
ing
16-92
BI
22
-
Current low
0=OK
, 1=Warn-
ing
16-92
BI
23
-
Profibus warning
0=OK
, 1=Warn-
ing
16-92
BI
24
-
Output frequency
limited
0=OK
, 1=Warn-
ing
16-92
BI
25
-
Current high
0=OK
, 1=Warn-
ing
16-92
BI
26
-
Feedback low
0=OK
, 1=Warn-
ing
16-92
BI
27
-
Feedback high
0=OK
, 1=Warn-
ing
16-92
BI
28
-
Reference low
0=OK
, 1=Warn-
ing
16-92
BI
29
-
10 Volt low
0=OK
, 1=Warn-
ing
16-92
BI
30
-
Live zero error
0=OK
, 1=Warn-
ing
16-92
BI
31
-
Phase loss
0=OK
, 1=Warn-
ing
16-92
BI
32
-
DC link voltage
high
0=OK
, 1=Warn-
ing
16-92
BI
33
-
DC link voltage low
0=OK
, 1=Warn-
ing
16-92
BI
34
-
DC link over volt-
age
0=OK
, 1=Warn-
ing
16-92
BI
35
-
DC link under volt-
age
0=OK
, 1=Warn-
ing
16-92
BI
36
-
VLT thermal
0=OK
, 1=Warn-
ing
16-92
BI
37
-
Motor thermal
0=OK
, 1=Warn-
ing
16-92
BI
38
-
Motor thermistor
0=OK
, 1=Warn-
ing
16-92
BI
39
-
Current limit
0=OK
, 1=Warn-
ing
16-92
BI
40
-
Over current
0=OK
, 1=Warn-
ing
16-92
BI
41
-
Standard bus time-
out
0=OK
, 1=Warn-
ing
16-92
BI
42
-
HPFB time-out
0=OK
, 1=Warn-
ing
16-92
BI
43
-
EEPROM error
power card
0=OK
, 1=Warn-
ing
16-92
3. Appendix
VLT
®
HVAC Drive Metasys N2
24
MG.11.G1.02 - VLT
®
is a registered Danfoss trademark
3